Braking, Safe Stopping and Troubleshooting

Mechanical and dynamic braking, safe torque off and stop categories, commissioning, and a symptom table for motion faults.

Brakes: holding and dynamic

There are two kinds of braking, and they are often confused. A holding brake is a mechanical device that locks the shaft when power is off; a dynamic (electrical) brake slows the motor under control, using the drive.

BrakeHow it worksUseLimit
Spring-applied, power-off holding brakeSprings clamp the discs; a coil releases them when poweredHolds vertical loads and parks the axis when power is lostNot for repeated dynamic stops: the friction lining wears. Rated for a few emergency stops
Permanent-magnet brakeMagnets clamp; a coil cancels them to releaseCompact holding brake for servo motorsHolding torque only; no wear in normal use
Dynamic braking resistorThe drive switches the regenerated energy into a resistorFast decelerations, lowering a loadHeat: the resistor must be rated for the energy and the repetition
Regenerative driveReturns the energy to the supplyFrequent braking, large energiesCostlier; needs a suitable supply
DC injection brakingDirect current in the motor stops itStopping induction motors without a resistorHeats the motor; works only at low speeds and low inertia
Short-circuit (motor leads shorted)Back-EMF drives a current that opposes motionA simple stop for small servo motors if the drive failsDoes not hold at standstill

Worked example: sizing a holding brake

  • The vertical axis of Sizing a Motion Axis holds a 20 kg load on a 10 mm lead ball screw (90 percent efficient): the static torque is 196.2 × 0.010 ÷ (2π × 0.9) = 0.347 N·m.
  • A common rule is to choose a holding brake with at least 1.5 times the static torque: 1.5 × 0.347 = 0.520 N·m. Compare the brake’s rating with the motor’s own peak torque too: a brake that is much stronger than the motor can be damaged by a runaway motor.
  • Emergency braking energy: the rotary table of the same example has an inertia of 2.20 × 10-4 kg·m² at the motor and turns at 600 rpm (62.8 rad/s): stopping it dissipates ½ J ω² = 0.4 J. With 20 stops an hour that is 9 J per hour: trivial, but at larger inertias the brake’s energy rating (J per stop and per hour) decides the life.
  • Always apply the brake only when the axis is stopped in normal operation, and keep the motor torque on until the brake has closed (a delay of 50 to 200 ms), or the load sags.

Stopping time and distance

How far the axis travels after a stop command is a safety distance as well as a mechanical one. The distance traveled is the speed times the reaction time plus the braking distance v² ÷ (2a).

Stopping functions: STO, SS1 and SS2 (speed against time)00.511.522.530.00.51.0time after the stop command (s)speed (fraction of running speed)stop commandSTO: torque off at once, the motor coastsSS1 and SS2: controlled ramp to zeroAfter SS1 the torque is removed (like STO); after SS2 the drive keeps holding position. A vertical load needs a brake with STO.
Three stopping behaviors: coasting after torque is removed, and a controlled ramp followed by holding or torque off.

Worked example: stopping distance of the ball-screw axis

  • At the cruise speed of 0.667 m/s a controlled stop at 5.0 m/s² takes v ÷ a = 0.13 s and covers v² ÷ (2a) = 0.044 m = 44 mm.
  • If the torque is simply removed (coast, STO) and only friction of about 0.5 m/s² decelerates the load, the distance is 0.444 ÷ (2 × 0.5) = 444 mm: nearly half a meter, and the axis could hit the end of travel. This is why a stop on a screw axis often needs a brake.
  • With a spring brake that reacts in 50 ms and decelerates at 8 m/s², the distance is 0.667 × 0.05 + 0.444 ÷ 16 = 61 mm.
  • Safety distance to a guard (ISO 13855) adds the speed of approach of a person times the total stopping time of the machine, so a shorter stop means a closer, more convenient guard.

Safe stopping functions

Modern drives include certified safety functions defined in IEC 61800-5-2. They are implemented in the drive’s safety hardware, with their own inputs, so that a software fault or an unwanted command cannot override them.

FunctionWhat it doesEquivalent stop
STO: Safe Torque OffRemoves the energy that can produce torque: the motor cannot be driven. It does not brake; the load coastsStop category 0
SS1: Safe Stop 1A monitored controlled deceleration to zero, then STOStop category 1
SS2: Safe Stop 2A monitored controlled deceleration, then the drive holds the position under supervisionStop category 2
SOS: Safe Operating StopThe drive holds position with the torque on, and monitors itMaintenance with the power on
SLS: Safely Limited SpeedMonitors the speed against a limitSet-up and jog with guards open
SBC / SBT: Safe Brake Control and TestControls the holding brake safely and tests itVertical axes
SDI, SLPSafe direction, safely limited positionMachine zones
  • STO is wired with two channels (two inputs, from a dual-channel safety relay or a safety PLC) and the drive reports a fault if they disagree. It is the cheapest way to remove the energy, and it replaces the output contactor.
  • A stop by the program or a normal stop command is not a safety function. It relies on software and on the drive working, which a safety function must not.
  • Brakes need a safe control (SBC) where a falling load could injure; test them regularly.
  • A drive with built-in safety over a fieldbus (Safety over EtherCAT / FSoE, CIP Safety, PROFIsafe) gives safe functions without extra wiring; see Industrial Ethernet.

Emergency stop, categories and performance level

TermMeaning
Stop category 0 (EN 60204-1)Immediate removal of power to the actuators: an uncontrolled stop
Stop category 1A controlled stop with power kept to the actuators until standstill, then power removed
Stop category 2A controlled stop with power left on at standstill
Emergency stopA complementary protective measure that must stop the machine quickly. It must be category 0 or 1, and not need the control software. A red mushroom button on a yellow background; latching, needs a deliberate reset
Performance Level (PL a to e) and SILThe reliability required of a safety function, from a risk assessment (ISO 13849-1, IEC 62061). Many emergency stops need PL d, with redundancy and monitoring
Risk assessmentIdentifies the hazards and the risk reduction needed. It comes first: the safety functions follow from it

Design safety with certified components (safety relays, safety PLCs, drives with STO) and with proper integration of the whole chain: the sensor, the logic and the actuator. A guard door with a safety interlock switch, a light curtain and an emergency stop all feed the same safety logic, which controls the drive’s STO and the brake. See PLC Troubleshooting, Safety and Documentation for the PLC side. This guide is not a substitute for the standards or for a qualified safety engineer.

Commissioning an axis

  • Verify the safety first: the emergency stop, STO and any limit switches work, with the motor uncoupled where possible.
  • Check the wiring and parameters: motor and encoder data, the supply voltage, the drive’s current limits, the direction of the feedback and of the command.
  • Move with the torque and speed limited, in jog mode, with a hand near the stop button. Confirm the direction and the scaling (does 10 mm commanded give 10 mm of travel?).
  • Set the limits: software travel limits inside the hardware limit switches, inside the mechanical stops. Test each.
  • Home the axis and check the repeatability (see Encoders, Resolvers and Feedback).
  • Auto-tune or tune (see Servo Systems and Tuning) with the real load, then check the step response and the following error at full speed.
  • Test the brake and the stops: hold test, and an emergency stop at full speed with a safe stopping distance.
  • Run a hot test at full duty and read the motor temperature and the drive’s torque against the calculation (see Sizing a Motion Axis).
  • Record everything: parameter file, wiring, test results and the safety validation, then save a backup of the drive and controller programs.

Lockout and stored energy

  • Isolate the energy (electrical, pneumatic, hydraulic, gravity, springs) and lock and tag the isolators before working on or in a machine. Try to start it to check.
  • Wait for the drive’s DC bus to discharge (often five minutes; follow the label) and measure it before touching a drive.
  • Support raised loads mechanically before working under them; a brake or a drive can fail.
  • Release springs and vent air or oil pressure before opening a circuit.
  • Safety standards: OSHA 1910.147 (lockout/tagout, US), ISO 14118 (preventing unexpected start-up), ISO 12100 (risk assessment).

Troubleshooting motion faults

SymptomLikely causeFirst check
Axis does not move, no faultNot enabled, a limit or STO input open, a brake not released, no commandDrive status and enable, the safety circuit, the brake voltage, the command source
Moves the wrong way or runs awayReversed feedback or command, wrong commutationFeedback direction and phasing, motor wiring (see Encoders, Resolvers and Feedback)
Following-error faultOverload, jam, low gains, current limit, brake draggingFree the axis by hand; torque and current limits; brake release
Overcurrent or overload faultToo short a ramp, a heavy or jammed load, wrong motor dataRamps, the mechanics, motor parameters
Overvoltage on decelerationRegeneration into the busLonger deceleration or a braking resistor (see AC Motors and Variable-Frequency Drives)
Vibration, noise, buzzGains too high, resonance, a loose couplingLower the gain, add notch filters, tighten the coupling (see Servo Systems and Tuning)
Motor or drive too hotTorque above the continuous rating, poor cooling, high ambient temperatureRMS torque from the drive, airflow, ambient temperature
Position errors that growLost counts or steps, slipping coupling, backlashEncoder signals, coupling, mechanical lash (see Mechanical Transmission: Screws, Belts and Gearboxes)
Vertical axis drops when disabledNo brake, or the brake is worn or not applyingBrake holding test, brake wiring and sequence
Intermittent faultsNoise, a poor connection, a failing cableShielding and grounding, connectors, cable flex points

Related

FAQ

Is the emergency stop button enough to make a machine safe?

No. It is one protective measure. A risk assessment decides what else is needed (guards, interlocks, light curtains, safe speed), and the whole chain must reach the required performance level.

Do I need STO if I have an emergency stop contactor?

A contactor in the motor supply works, but an STO input is cheaper, faster, has no contact wear and keeps the DC bus charged for a quick restart. Many standards accept either when correctly wired and validated.

Why does my vertical axis sag before the brake closes?

The brake takes time (tens of milliseconds) to engage. Keep the torque on until the brake has closed, and release it only after the torque is established when starting.

How often should brakes be tested?

Follow the manufacturer and the risk assessment: commonly at each start-up of a vertical axis or at set intervals, by applying a test torque with the brake closed and checking for no movement.

References

  • IEC 61800-5-2, Adjustable speed electrical power drive systems: safety requirements, functional.
  • ISO 13849-1 (safety-related parts of control systems), IEC 62061, EN 60204-1 (electrical equipment of machines), ISO 12100 and ISO 13855.
  • Drive and brake manufacturers’ safety manuals (Siemens SINAMICS Safety Integrated, Rockwell, Kollmorgen, Warner Electric brakes).

Last reviewed: October 2026. This page is an introduction, not a substitute for the applicable standards or a qualified safety assessment of your machine.