HVAC and Psychrometrics

Comfort, the psychrometric chart and its processes, heating and cooling loads, ventilation, ducts and fans, chillers and cooling towers, hydronic systems and controls, with worked numbers.

Heating, ventilating and air conditioning keeps people comfortable and healthy, and keeps equipment and processes within limits, and it is one of the largest uses of energy in any building. The subject rests on one set of ideas: air is a mixture of dry air and water vapor, so every process has a sensible part that changes the temperature and a latent part that changes the humidity; and every system is a chain of heat balances, from the room through the air, the water and the refrigerant to the outdoors. This guide covers comfort and system types, the psychrometric chart and its processes, heating and cooling loads, ventilation and air quality, ducts and fans, chillers and cooling towers, hydronic systems, and controls, energy and troubleshooting. One 100 m² office, with its loads and equipment, runs through every page, and every number is computed. The thermodynamics behind it is in Thermodynamics and Steam.

Start here: what do you need?

I need to…Go to
understand comfort, system types and the basic numbersHVAC Basics and Thermal Comfort
find dew point, wet bulb, enthalpy or read the chartMoist Air and the Psychrometric Chart
work out a coil, humidifier, mixing box or evaporative coolerPsychrometric Processes
calculate a heating or cooling load and the supply airflowHeating and Cooling Load Calculations
choose ventilation rates, check CO₂, size heat recoveryVentilation and Indoor Air Quality
size ducts, pick a fan or understand fan lawsDucts, Fans and Air Distribution
size a chiller loop and cooling towerCoils, Chillers and Cooling Towers
size radiators, pipes, pumps and expansion vesselsHydronic Heating and Cooling
understand controls, estimate annual energy or diagnose a faultControls, Energy and Troubleshooting

A suggested order

Start with HVAC Basics and Thermal Comfort and Moist Air and the Psychrometric Chart. Psychrometric Processes and Heating and Cooling Load Calculations use them to size the air side, and Ventilation and Indoor Air Quality and Ducts, Fans and Air Distribution move the air. Coils, Chillers and Cooling Towers and Hydronic Heating and Cooling cover the water side, and Controls, Energy and Troubleshooting ties it together.

  1. HVAC Basics and Thermal Comfort: What HVAC does, the comfort zone, how a building is conditioned, the main system types and the numbers to remember.
  2. Moist Air and the Psychrometric Chart: Humidity ratio, relative humidity, dew point, wet bulb and enthalpy, how to read the chart and how to calculate every property.
  3. Psychrometric Processes: Sensible heating and cooling, cooling and dehumidifying coils, humidifying, mixing air streams and evaporative cooling, with worked examples.
  4. Heating and Cooling Load Calculations: Heat loss, solar and internal gains, ventilation load and the sensible and latent split, worked for a 100 square meter office.
  5. Ventilation and Indoor Air Quality: Ventilation rates, carbon dioxide as an indicator, air changes, infiltration, filters and heat recovery.
  6. Ducts, Fans and Air Distribution: Duct sizing, friction and fitting losses, fan curves and fan laws, diffusers and balancing.
  7. Coils, Chillers and Cooling Towers: Chilled-water flow, chiller COP, condenser water, cooling tower range and approach, and water use.
  8. Hydronic Heating and Cooling: Water-based heating and cooling, flow and temperature difference, pipe sizing, emitters, expansion vessels and pumps.
  9. Controls, Energy and Troubleshooting: Thermostats and control loops, economisers, variable air volume, balance point and degree days, and a table of common problems.

One office, from load to plant

Peak cooling load of the example office, by sourceSolar through glass2 640 WLighting1 000 WEquipment800 WPeople (sensible)750 WVentilation air (sensible)563 WVentilation air (latent)515 WPeople (latent)550 WGlass conduction302 WWall conduction154 WTotal 7.27 kW: sensible 6.21 kW and latent 1.06 kW. Blue bars are latent load; gray and orange bars are sensible.
The peak cooling load of the example office, by source.

Worked example: the same office on every page

Quick reference: the equations

What you needEquation
Humidity ratioW = 0.622 pw ÷ (p − pw)
Enthalpy of moist airh = 1.006 T + W (2 501 + 1.86 T)
Sensible heat of airQ (W) = 1.2 × flow (L/s) × ΔT (K)
Latent heat of airQ = ṁ ΔW × 2 501 kJ/kg
Heat in waterQ (kW) = 4.186 × flow (kg/s) × ΔT (K)
MixingWm and hm are mass-weighted averages
Room CO₂C = Cout + G ÷ Q (steady state)
Duct frictionΔP ÷ L = f ÷ D × ρ v² ÷ 2
Fan lawsQ ∝ N, ΔP ∝ N², P ∝ N³
ChillerW = Q ÷ COP; heat to tower = Q + W
Annual heatingE = UA × HDD × 24

Related guides and tools

Safety first

  • Refrigerants can be flammable, toxic or asphyxiating, and are regulated; only qualified people should open a refrigerant circuit.
  • Legionella grows in warm stored water, cooling towers and humidifiers. Keep water moving, treated and clean, and follow the local code.
  • Combustion appliances make carbon monoxide: keep flues, air supply and alarms working, and never block a ventilation opening.
  • Electrical, rotating and hot parts: isolate and lock out before opening a unit, and never bypass a safety control.
  • Pressure and heights: hot water, steam and refrigerant systems are pressure equipment; roof units and ducts mean working at height.
  • The numbers here are for study and preliminary design. Real projects need the local codes, a competent designer and commissioning.

FAQ

Where do I start with HVAC design?

Read HVAC Basics and Thermal Comfort, then Load Calculations. The load sets the air, water and plant sizes.

Why does humidity matter so much?

It sets the latent load (a large share of the cooling load in humid climates), affects comfort and mold, and is why a cooling coil has to be colder than the room needs for temperature alone.

Can I use a rule of thumb for equipment size?

For a first estimate, yes (see Load Calculations). Always calculate before ordering equipment.

Where are hydraulics and pneumatics?

They are the last guide in the Thermal and Fluids section (the actuator side is in the Motion Control guide).

References

  • ASHRAE, Handbook (Fundamentals, HVAC Systems and Equipment, HVAC Applications, Refrigeration), and ASHRAE Standards 55, 62.1 and 90.1.
  • CIBSE Guides A, B, C and H; McQuiston, F. C., Parker, J. D., Spitler, J. D., Heating, Ventilating, and Air Conditioning: Analysis and Design, Wiley.
  • Kreith, F., Manglik, R., Bohn, M., Principles of Heat Transfer; Çengel, Y. A. and Boles, M. A., Thermodynamics: An Engineering Approach.
  • EN 16798, EN 12831, EN 12828, ISO 7730, ISO 52016.

Last reviewed: November 2026. Values are typical; check the standard, the manufacturer’s data and the code that applies to your project.