Cabling, Grounding and Noise

Cable types and connectors, shielding and grounding, routing, fiber, and an installation checklist.

Cable types by network

Every network standard names its cable, and for good reason: the impedance, capacitance, shielding and twist are part of the design. General-purpose wire is the most common cause of a network that “should” work but does not.

NetworkCableImpedanceConnectorNotes
RS-232Shielded multicore, low capacitancen/aDB9, DB25, terminalsUnder 15 m at 9 600 baud
RS-485 / Modbus RTUShielded twisted pair, 24 AWG, low capacitance (Belden 9841 or equivalent)120 ΩTerminals, DB9, M12Daisy chain; third conductor for the reference
PROFIBUS DPViolet cable, one shielded twisted pair (type A)150 ΩD-sub 9 with terminator switch, M12 B-codedStrip length and shield contact matter
DeviceNetThick (round, 15 AWG power pair) or thin (18 AWG) cable with signal and power pairs120 ΩOpen style, M12 or miniTrunk and drop lengths limited by speed
CANopenShielded twisted pair, 120 Ω120 ΩD-sub 9, M12 A-codedTerminate at both ends
AS-InterfaceYellow profiled flat cable (data and power), black for auxiliary powern/aPiercing connectors, M12Polarity is fixed by the profile
IO-LinkStandard unshielded 3-wire M12 sensor cablen/aM12 A-coded20 m maximum
Ethernet 100BASE-TXShielded twisted pair, 4-pair (Cat5e) or 2-pair (industrial Cat5)100 ΩRJ45, M12 D-codedSolid for fixed, stranded for flexing
Gigabit EthernetCat5e or Cat6, 4 pairs, shielded in industry100 ΩRJ45, M12 X-codedAll four pairs used
PROFINETType A (fixed), B (flexible), C (continuous flexing) cable in green sheath100 ΩRJ45 IP20, IP67 push-pull, M12Four-core for 100 Mbit/s
EtherNet/IPAs industrial Ethernet, often in a yellow or blue sheath100 ΩRJ45, M12Follow ODVA cable guidelines
EtherCATStandard Cat5e or better100 ΩRJ45, M8, M12100 m between nodes
4–20 mA, 0–10 V analogShielded twisted pair, instrument cablen/aTerminalsShield at one end (the receiving end); twist reduces pick-up

RS-485 and fieldbus cable in detail

PropertyWhy it mattersTypical for RS-485
Characteristic impedanceMust match the terminators; a mismatch reflects signals120 Ω
CapacitanceRounds the edges; limits speed and lengthAbout 40 pF per meter or lower for the pair
TwistMakes noise cancel in the pairTight, uniform twist, about 1 turn per 2 cm
Conductor sizeResistance over long runs; strength24 AWG (0.25 mm²) common; 22 AWG for long runs
ShieldBlocks electric-field noiseFoil plus drain wire, or braid
Third conductorThe common referenceIn a three-conductor cable, or a second pair
Temperature and flex ratingCable stays intact in servicePVC for fixed, PUR for flex and oil

A Cat5e Ethernet cable is often used for short RS-485 runs: one twisted pair for A and B (with the standard 100 Ω impedance, acceptable at moderate speeds) and another for the reference. It works at 9 600 baud over modest distances, but a proper 120 Ω RS-485 cable is better for long or fast runs. Never split a twisted pair across two different pairs: the noise rejection is lost.

Ethernet cable: categories, construction and channel length

CategoryBandwidthUsed forNotes
Cat5e100 MHz100 Mbit/s and 1 Gbit/sThe industrial minimum
Cat6250 MHz1 Gbit/s, 10 Gbit/s to 55 mLarger diameter; harder to terminate
Cat6A500 MHz10 Gbit/s to 100 mBackbones and vision systems
Cat7 and higher600 MHz and upSpecial useNeeds non-RJ45 connectors for full performance
ConstructionMeaningWhen to use
UTPUnshielded twisted pairOffice; clean control rooms only
F/UTP, FTPOverall foil shieldIndustrial default for panels
S/FTP, SF/UTPBraid and foil shieldsHeavy noise; near drives
Solid conductorsOne copper strand per conductorFixed installation: lower loss, but breaks if flexed
Stranded conductorsSeveral strandsPatch cords and flexible runs; about 20 percent higher attenuation
Drag-chain / continuous-flex (PROFINET type C)Special stranding and PUR jacketCable carriers, robots

Worked example: the 100 m channel

  • The standard 100 m limit is for a channel with up to 90 m of fixed (solid) cable and up to 10 m of patch cords. Stranded patch cords have about 20 percent more attenuation, so each meter of patch cord counts as 1.2 m of solid cable.
  • With 10 m of patch cords the fixed cable may be no longer than 100 − 1.2 × 10 = 88 m.
  • With 20 m of patch cords (flexible runs at both ends) the limit falls to 100 − 1.2 × 20 = 76 m.
  • A flexible industrial cable has higher attenuation again: check the manufacturer’s maximum length (often 50 to 80 m for a continuous-flex cable).
  • Beyond this, add a switch or a media converter at the limit (a switch is a repeater that restarts the 100 m), or use fiber.

Connectors

RJ45 (T568B) to M12 D-coded for 10/100 Mbit/s EthernetRJ45 plug (pins 4, 5, 7, 8 unused at 100 Mbit/s)M12 D-coded plugpin 1 TX+white/orangepin 2 TX-orangepin 3 RX+white/greenpin 6 RX-greenpin 1 TX+pin 2 RX+pin 3 TX-pin 4 RX-The pairs follow the same signals, so a straight M12-to-RJ45 patch cable joins the matching names (TX to TX at the connector;the switch crosses internally, or auto-MDI/MDIX does it). Gigabit uses all eight RJ45 pins or 8-pin X-coded M12.
RJ45 (T568B) pins and the 4-pin M12 D-coded connector used for 100 Mbit/s industrial Ethernet.
ConnectorUsed forRatingNotes
RJ45, IP20Panel Ethernet, inside the cabinetIP20Use latching boots; do not use office plugs where vibration is present
RJ45 push-pull (IP67)Ethernet on the machine, outside the cabinetIP65/67Common on PROFINET field devices
M12 D-coded, 4 pin100 Mbit/s Ethernet (PROFINET, EtherNet/IP, EtherCAT)IP67Screw thread; keyed so it cannot be mixed up with A-coded
M12 X-coded, 8 pinGigabit EthernetIP67Shielded; keyed
M12 A-coded, 4 or 5 pinSensors, IO-Link, DeviceNet, CANopenIP67Power and signal
M12 B-coded, 5 pinPROFIBUSIP67Marked violet
M8Small sensors, EtherCAT in tight spacesIP67Fine thread
D-sub 9 (DB9)RS-232, PROFIBUS, CANIP20Screw-locked; the shield is on the shell
Screw or spring terminalsRS-485, analog, powerIP20Ferrules on stranded wire; check the strip length
  • Crimping and termination quality is a leading cause of intermittent faults: use the right tool and the connector made for that cable; follow the manufacturer’s stripping dimensions.
  • Keep the shield intact through the connector with a 360-degree contact.
  • Mark the ports and use connector colors to keep networks from being mixed up (for example green for PROFINET, yellow for EtherNet/IP).
  • Strain relief and bend radius. A sharp bend or a pulled connector damages the pairs; use at least 8 times the cable diameter for fixed cable, more for flexing.
  • Cap or plug unused ports, especially M12, to keep out dust and water.

Routing and separation

Cross-section of a cable duct or trayPowermotor, VFD output24 V controlI/O, relaysSignalEthernet, fieldbusSeparate the groups with metal dividers, orkeep at least 200 mm between power andcommunication cable (more near drives).Use shielded cable on the motor side of a VFD,as short as possible.Where cables must crosspower cablecommunication cableCross at 90 degrees: the coupling is least.Parallel runs couple the most noise.Other rules: leave cables unbundled where they run next to a VFD; keep fluorescent, welding and contactor wiring away fromsignal cable; use metal conduit or tray bonded to the panel; leave 30 percent spare capacity; mark both ends of every cable.Fiber has none of these problems: use it between cabinets, across large ground differences and next to heavy drives.
Separating power, control and signal cables, and crossing them at 90 degrees.
Cable groupExamplesTreat as
PowerMains, motor and VFD output cables, contactors, heaters, weldersNoise sources
Control24 V DC digital I/O, relay and solenoid wiringMild noise sources
Signal and communicationEthernet, fieldbus, RS-485, analog signals, encodersSensitive
  • Separate the groups with metal dividers, or keep at least 200 mm between power and communication cable when they run parallel for a long distance; more near a drive output.
  • Cross at 90 degrees when different groups must cross.
  • Use metal trays and conduits, bonded to the panel at both ends; a closed steel conduit is an excellent screen.
  • Do not run communication cable in the same bundle as the motor cable. Do not coil excess length next to power wiring.
  • In the cabinet, put the drive and its filter at one side, the PLC and communication modules at the other, and keep the wiring from touching.
  • Avoid sources: fluorescent light ballasts, welders, large contactors, transformers and radio equipment.

Shielding and grounding

A shield blocks electric-field noise by carrying it to ground before it reaches the signal wires. It works only if it is connected properly. The rules differ with frequency: at low frequencies (50/60 Hz hum) grounding at one end avoids a ground loop; at high frequencies (drives, radio, fast digital edges) the shield must be grounded at both ends, with a 360-degree clamp rather than a “pigtail”, and the two grounds must be bonded together so the shield does not carry the equalizing current.

Cabinet ACabinet Bcable with shieldopenOne end grounded: stops low-frequency hum and avoids a ground loop; weak against radio-frequency noiseCabinet ACabinet Bcable with shieldground-loop current flows along the shieldBoth ends grounded: blocks high frequencies, but a ground difference drives a loop current: hum and noiseCabinet ACabinet Bcable with shieldequipotential bonding conductor takes the ground current insteadBoth ends, bonded: 360-degree clamps and a heavy equipotential bond: the standard for drives and Ethernet
Shield grounded at one end, at both ends, and at both ends with an equipotential bonding conductor.
CableShield practiceWhy
Analog signals (4–20 mA, 0–10 V)Ground at one end, normally the receiving (PLC) endAvoids hum from a ground loop at low frequency
RS-485 and fieldbusGround at each node through a short connection (or one end plus capacitors), with the panels bondedFollow the network’s rules; PROFIBUS grounds the shield at every connector
Ethernet, industrialShield connected at both ends through the RJ45 or M12 housingHigh-frequency noise; equipotential bonding between panels
VFD motor cableShield grounded at both ends with 360-degree clamps (drive and motor)Carries the common-mode current back to the drive

Ground loops and equipotential bonding

Two panels with a few volts between their grounds, joined by a signal cable with its shield (or a common conductor) connected at both ends, let current flow through the cable and cause hum and bit errors. Remedies: run a heavy equipotential bonding conductor beside the cable, so that most of the current takes it (often a 16 mm² or larger copper strap); use isolated ports; or break the connection with fiber. Bonding the panels is the right fix for noise; isolation is the right fix for safety and for unbonded systems.

Variable frequency drives: the biggest noise source

A VFD switches its output between two voltage levels thousands of times a second, with very fast edges. The long motor cable acts as an antenna, and the cable capacitance gives a high-frequency common-mode current that returns through ground, the shield and any other nearby conductor, including communication cables.

Worked example: the capacitance of a motor cable

  • A shielded motor cable has a capacitance of about 200 pF per meter between each conductor and the shield. A 50 m run has about 200 × 50 = 10 000 pF = 10 nF to ground on each conductor.
  • Each switching edge charges and discharges this capacitance, so the drive’s output carries a spike of current at every transition (a few amperes for a fast edge on a high bus voltage). That is the noise the shield and the bonding must carry.
  • Doubling the cable length doubles the capacitance and the current: keep the motor cable as short as the installation allows, and fit output filters (dV/dt or sine filters) on long runs.
MeasureWhat it does
Shielded motor cable, 360° bonded at both endsContains the noise and returns it to the drive
Drive and filter on a bare metal panelA good high-frequency ground plane
Line reactors, EMC (RFI) filtersReduce noise on the supply side
Output (dV/dt or sine) filtersSlow the edges on long motor cables
FerritesReduce common-mode current on a cable (a help, not a cure)
Separate routingMotor cable apart from communication cable
Lower carrier frequencyFewer, less intense switching events, at the cost of motor noise

Fiber optic cable

Optical fiber carries light, not current, so it is immune to electrical noise, lightning and ground differences, and is the right choice between buildings, across drives and for long runs. Its limits are cost, careful termination and bend radius.

TypeCore / wavelengthTypical reach at 100 Mbit/s to 1 Gbit/sUse
Multimode, OM1/OM262.5 or 50 µm, 850 nm and 1300 nm2 km at 100 Mbit/s, about 275 to 550 m at 1 Gbit/sWithin a plant or building
Multimode, OM3/OM450 µm, 850 nmAbout 300 to 550 m at 1 Gbit/s; far more at 10 Gbit/sBackbones
Single-mode9 µm, 1310 nm and 1550 nm10 km and beyondBetween buildings and sites
Plastic optical fiber (POF)980 µm core, 650 nmTens of metersSensors and short links in noisy places
Link budget for 10 km of single-mode fiber at 1310 nm (typical values)Transmitter output-15.0 dBmFiber: 10 km x 0.35 dB/km-3.5 dB4 connectors x 0.5 dB-2.0 dB4 splices x 0.1 dB-0.4 dBPower at the receiver-20.9 dBmReceiver sensitivity-31.0 dBm0 dBmMargin = received power – receiver sensitivity = -20.9 – (-31) = 10.1 dB. Keep at least 3 dB spare for aging, dirt and repairs.Multimode (850 nm, 62.5/125 or 50/125) reaches about 300 to 550 m at 1 Gbit/s; single-mode reaches 10 km and more. Clean connectors first.
A link budget for 10 km of single-mode fiber: the margin is what is left after all the losses.

Worked example: a link budget

  • A single-mode transmitter sends -15.0 dBm; the receiver needs at least -31.0 dBm. The budget is 16.0 dB.
  • The losses on a 10 km link: fiber 10 × 0.35 = 3.5 dB, four connectors at 0.5 dB = 2.0 dB, four splices at 0.1 dB = 0.4 dB. Total 5.9 dB.
  • Received power -15.0 − 5.9 = -20.9 dBm; margin -20.9 − (-31.0) = 10.1 dB. Keep at least 3 dB for aging, dirt and later repairs: this link has plenty.
  • For 500 m of multimode at 850 nm (about 3 dB per km, two connectors): 1.5 + 1.0 = 2.5 dB, well within a typical 8 to 10 dB budget.
  • The commonest fiber fault is a dirty connector: clean with a lint-free wipe or a click-cleaner before every mating, and never look into a fiber or a transmitter (invisible infrared).
  • Media converters and SFP modules join copper and fiber; match the wavelength and mode on both ends and use the right pair of fibers (transmit to receive).
  • Bend radius is about 10 times the cable diameter (or 30 mm for bare fiber) when installed.
  • Fiber is not unbreakable: protect it from crushing and from being pulled by its connectors.

Environment: flexing, oil, heat and ingress

ConditionChooseAvoid
Continuous flexing (drag chain, robot)Cable rated for continuous flex (PROFINET type C, PUR jacket, fine stranding)Solid-core or office patch cords
Oil, coolant, chemicalsPUR jacket, oil-resistant (check the specific fluid)PVC
HeatRated cable (for example 90 °C or higher; PTFE for very hot places)Standard PVC near hot surfaces
ColdLow-temperature rated PURStandard PVC (stiff, cracks)
Outdoor and UVUV-resistant jacket, gel-filled or armored for burialIndoor cable
Washdown, foodIP67/IP69K connectors and cables, stainless housingsOpen terminals
Hazardous areasApproved cable and glands for the zone; intrinsically safe segmentsAnything not certified
Rodents, crushingArmored cable or conduitBare cable on the floor

Ingress ratings: IP20 is finger-safe in a cabinet; IP65 is dust-tight and protected against water jets; IP67 survives temporary immersion; IP69K survives high-pressure steam cleaning. The connector, the cable gland and the device must all meet the rating.

Worked example: voltage drop on a DeviceNet-style trunk

  • A thick-cable trunk of 100 m, with a conductor resistance of about 5.4 mΩ per meter, carries 3.6 A to the devices at the far end.
  • The 24 V loop goes down one conductor and back on the other: drop = 3.6 A × 2 × 0.0054 Ω/m × 100 m = 3.89 V (about 16.2 percent of 24 V).
  • DeviceNet specifies a maximum drop of 5 V per conductor and the devices need at least 11 V; this trunk is fine. Where many outputs switch at once, measure the voltage at the last device under full load.

Testing and certifying cable

TestToolWhat it finds
Continuity and wire mapSimple cable testerOpens, shorts, crossed or split pairs
Length and TDRCable tester with time-domain reflectometerWhere a break is, and the length
CertificationCertifier (Fluke DSX and similar)Attenuation, crosstalk, return loss to the category; a printed report for the customer
Resistance across the pair (RS-485)Multimeter, power offAbout 60 Ω with two terminators
Insulation resistanceMegohm meterDamaged cable, water ingress (not on live networks)
Fiber power and lossOptical power meter and light source, or OTDRLink loss, where the loss occurs
Bus test (PROFIBUS)PROFIBUS testerSignal level, reflections, terminator, address list
Live signalOscilloscope, protocol analyzerNoise, reflections, errors: see Sniffers, Analyzers and Serial Tools

Installation checklist

  • Drawings and labels: every cable has a number at both ends and appears on the drawings.
  • Right cable for each network, in the right jacket for the environment.
  • Routes checked against the separation rules; no communication cables beside motor leads.
  • Connectors terminated with the right tool; shield contact complete; strain relief in place.
  • Terminators fitted and counted (RS-485, PROFIBUS, CAN: two per segment).
  • Shield and bonding done as the network requires; the equipotential bond fitted.
  • Length and node limits within the specification, with margin.
  • Test results recorded for every cable (continuity at least, certification where required).
  • Spare capacity: spare conductors and conduit space.
  • Unused ports capped.
  • As-built documents updated and a copy left in the panel.

Common mistakes

MistakeWhat you seeFix
General-purpose wire for RS-485 or PROFIBUSErrors at higher baud rates or long runsUse the specified cable
Communication cable bundled with motor cableRandom errors when the drive runsSeparate by 200 mm or more; use conduit
Shield connected at one end only on a noisy siteRadio-frequency noise gets inBond both ends with 360° clamps, add equipotential bonding
Shield grounded at both ends with no bondingHum, ground-loop currentAdd a bonding conductor, or isolate
Solid-core cable in a moving machineIntermittent faults, then a breakUse continuous-flex cable
RJ45 plug crimped on stranded cable meant for solidIntermittent connectionMatch plug and cable; test
Pairs split in an RJ45 (wired 1-2, 4-5 with the pairs wrong)Works at 10 Mbit/s but not 100 or 1000Wire to T568A or B; certify
Bend radius ignored on fiberHigh loss, dead linkRe-route; use the bend-insensitive type
Dirty fiber connectorHigh loss, intermittent linkClean, inspect
No labelsHours lost tracingLabel both ends

Related

FAQ

Can I use office Ethernet cable on a machine?

For fixed runs inside a clean cabinet, yes (a shielded one is better). For flexing, oil, vibration or noise, use industrial cable and connectors.

Should the shield be grounded at one end or both?

For low-frequency hum on analog signals, one end. For drives and high-speed networks, both ends with 360-degree clamps and an equipotential bond. Follow the network standard.

How far from power cable should communication cable be?

At least 200 mm when running side by side for a long distance, crossing at 90 degrees where they meet, and in separate metal compartments if you can. Near a VFD output, go further.

Why does an Ethernet link work at 10 Mbit/s but not at 100?

A damaged cable pair or a split pair: the lower speed uses lower frequencies and tolerates faults that 100 Mbit/s does not. Replace or certify the cable.

When do I choose fiber?

Between buildings, across large ground differences, next to heavy electrical equipment, for lengths above 100 m, and wherever lightning is a risk.

References

  • ANSI/TIA-568.2-D, Balanced Twisted-Pair Telecommunications Cabling and Components Standards; ISO/IEC 11801, Generic cabling for customer premises.
  • PROFIBUS & PROFINET International, PROFINET Cabling and Interconnection Technology and PROFIBUS Installation Guideline.
  • ODVA, Media Planning and Installation Manual for EtherNet/IP (PUB00148).
  • IEC 61918, Industrial communication networks: Installation of communication networks in industrial premises; IEC 61000-5-2, Earthing and cabling (EMC).
  • Ott, H. W., Electromagnetic Compatibility Engineering, Wiley.
  • NFPA 79, Electrical Standard for Industrial Machinery; IEC 60204-1.

Last reviewed: October 2026. Speeds, lengths, node counts and menu names are typical: confirm against the specification and the manufacturer’s documentation for the devices you use.