Sniffers, Analyzers and Serial Tools
USB serial adapters, loopback plugs, terminal and Modbus tools, serial and Ethernet sniffing, Wireshark and scope checks.
On this page
- A method that works
- USB serial adapters
- Loopback plugs, breakout boxes and null modems
- Terminal and master/slave test software
- Sniffing a serial link
- Meter and oscilloscope checks
- Reading a Modbus capture
- Symptoms and likely causes
- Sniffing Ethernet with Wireshark
- Getting the traffic: mirror ports and taps
- Other network tools
- Cautions
- FAQ
A method that works
When a link will not come up, resist changing several things at once. Work from the bottom layer up, and prove each layer before moving on: power and wiring, then electrical signal, then settings, then protocol and addresses, then the PLC program. A cheap USB adapter and a free program can answer, in minutes, the question “is the device talking at all?”, which can otherwise take hours of guessing inside the PLC software.
| Question | Tool that answers it |
|---|---|
| Is there a voltage on the line, and the right polarity? | Multimeter |
| Is the line idle, and are there pulses when data is sent? | Multimeter (AC/DC scale), oscilloscope |
| Does the device answer a simple request? | PC with a USB adapter and a master tool |
| What bytes are really on the wire, in both directions? | Serial sniffer, logic analyzer, oscilloscope with decode |
| Is the Ethernet device reachable? | Ping, ARP, port scanner |
| What is the PLC really sending? | Wireshark on a mirror port or a tap |
USB serial adapters
Modern laptops have no serial port, so a USB adapter is the first tool to buy. Buy two or three: a USB-RS232 for programming ports and old equipment, a USB-RS485 for Modbus and drive networks, and a spare so you can build a sniffer.
| Chip | Notes |
|---|---|
| FTDI FT232R / FT232H | The reference choice: stable drivers, good isolation options, programmable. Counterfeit chips exist and some driver versions refuse them |
| Silicon Labs CP210x | Reliable, widely used, good drivers |
| WCH CH340 / CH341 | Cheap and common; fine for most work; the quality of the driver install varies |
| Prolific PL2303 | Many counterfeit chips: a recent driver may refuse them (a yellow warning in Device Manager). Buy from a source you trust, or avoid |
- Buy isolated for plant work. An isolated adapter protects the laptop from ground differences and surges. It costs more, but a ground loop between a laptop and a VFD panel can destroy an unisolated port.
- Check the voltage levels. A “USB-serial” cable for a microcontroller is often 3.3 V or 5 V TTL, not RS-232. Plugging it into a ±12 V RS-232 port can damage it. Make sure the adapter says RS-232, RS-422 or RS-485.
- RS-485 direction control. Good adapters switch the driver on and off automatically. A cheap one may need the software to control RTS, or it leaves the line driven and blocks the other devices.
- Terminal blocks or a DB9. Screw terminals are easier to use for A, B and ground than a DB9 with a gender changer.
- Label the COM port. Windows assigns a new port number to each adapter on each USB port; note it in Device Manager and label the adapter.
Loopback plugs, breakout boxes and null modems
| Item | What it is | What it proves |
|---|---|---|
| Loopback plug | A DB9 with pin 2 joined to pin 3 (and RTS to CTS, DTR to DSR) | The PC port and the driver work: what you type comes back |
| RS-485 loopback | A and B joined to a second adapter’s A and B on the same PC | Two adapters can talk; the software is set up correctly |
| Breakout box | A DB9 in-line with LEDs and jumpers for each line | Which lines are active; swap TXD/RXD without a soldering iron |
| Null modem adapter | Crosses TXD and RXD (pins 2 and 3) | Whether a straight or crossed cable is needed |
| Gender changer | Male–male or female–female DB9 | Makes a cable fit; says nothing about the signals |
Worked example: proving the PC side with a loopback
- Join pins 2 and 3 of the adapter’s DB9 with a paper clip or a jumper.
- Open a terminal program, select the adapter’s COM port, 9 600 baud 8N1, and type some letters.
- The letters appear on the screen only because they come back through the loopback. If they do, the adapter, driver and software are fine; the fault is in the cable, the device or its settings.
- Remove the loopback: the typing stops echoing. This confirms that the echo was the loopback, not the terminal’s local echo.
Terminal and master/slave test software
| Tool | Use | Notes |
|---|---|---|
| PuTTY, Tera Term | Simple serial terminals | Good for text protocols and quick tests; set the port, speed and parity |
| RealTerm | Terminal with a hex display | Shows bytes in hex and ASCII; can send hex strings and capture to a file |
| Docklight | Serial tester and logger | Send scripted sequences, log both directions with time stamps; free for limited use |
| Modbus Poll / Modbus Slave | Modbus master and slave simulators (commercial, trial available) | Reads and writes registers; shows the raw frames and error counts |
| QModMaster | Free, open-source Modbus master | RTU and TCP; adequate for quick checks |
| mbpoll | Free command-line Modbus master | Scriptable; works on Windows, Linux and Raspberry Pi |
| Vendor tools | Drive and PLC software | Many drive tools show the communication status and error counts |
- Be the master yourself. Disconnect the PLC from the bus (two masters on one bus corrupt each other’s frames), connect the PC, and read a known register. If the PC gets an answer, the device, wiring and settings are good.
- Be the slave. If the PLC is the master and you doubt it, connect the PC as a slave simulator with the same address and watch whether requests arrive.
- Change one setting at a time and note the result. Writing down the sequence keeps you from going around in circles.
Sniffing a serial link
A sniffer listens to a conversation between two devices without taking part. On a serial link there are three approaches.
| Method | How | Good for | Limits |
|---|---|---|---|
| RS-485 (party line) | Connect a USB-RS485 adapter to the A/B pair and set it to receive only | Modbus RTU: master and slaves share the same wires, so one adapter sees both directions | Add it with a short stub; do not add a third terminator; the adapter must not drive the line |
| RS-232 tap with two adapters | A Y-cable or breakout: the PC’s RXD pins listen to the PLC’s TXD and the device’s TXD on separate COM ports | Any RS-232 link | Two ports, two logs to merge by time stamp; do not connect the PC’s transmit pins |
| Software port monitor | Watch a COM port that a program on the PC is already using | Debugging what the PC software is sending | Only sees the PC’s own traffic |
| Logic analyzer | Clip leads on the TX/RX lines or the 5 V/3.3 V UART side; decode UART or Modbus | Timing, gaps, and signals the PC adapter cannot capture | Needs logic-level signals; use an RS-485 receiver or a differential probe |
| Oscilloscope with serial decode | Probe the line; the scope decodes UART | Seeing signal quality at the same time as the bytes | Differential signals need two channels or a differential probe |
- Receive only. A tap must never transmit on the line. On RS-232 leave the sniffer’s TXD unconnected; on RS-485 turn off its driver (receive only).
- Time stamps. With two adapters, log with time stamps so the two directions can be put in order.
- Same settings. The sniffer must use the same baud rate and parity as the link, or it shows garbage even when the link is fine.
- Capture to a file. A log you can search and send to the manufacturer is worth more than a moving screen.
Meter and oscilloscope checks
With a multimeter
| Measurement | Expected | What a wrong reading means |
|---|---|---|
| Idle voltage A to B (power on, no traffic) | About +0.2 to +5 V with bias; B positive of A on most devices | About 0 V means no bias, and a noisy line; a negative reading means A and B are swapped on the meter or on the bus |
| Resistance across A and B (power off) | About 60 Ω with two 120 Ω terminators | About 120 Ω: only one terminator; very high: none; very low: a short or too many terminators |
| Voltage during traffic (DC scale, averaging) | The reading flickers slightly | A steady reading means no traffic; frozen at a rail means a device is holding the line |
| RS-232 idle (TXD to ground) | About −5 to −12 V when idle | About 0 V: port off or unconnected; +V: wrong polarity or an RS-485 port |
| Ground difference (between the two devices’ grounds) | Under a few volts | More than a few volts: the common-mode range is exceeded; add a ground wire or isolation |
| Shield continuity | Continuous end to end, grounded at one point | Broken shield or grounded at both ends in a noisy plant |
With an oscilloscope
- Bit time. At 9 600 baud one bit is 104 µs. Measure the shortest pulse; if it is half or double, the baud rate is wrong by that factor.
- Idle level. The line should sit at a clean idle (mark) level between frames. A mid-level line is floating: add bias.
- Edges. Rounded, slow edges mean too much capacitance (a long cable or no matching termination); ringing after each edge means reflections (a missing or doubled terminator, or a long stub).
- Amplitude. RS-485 should show at least ±1.5 V differentially at the receiver. Much lower means a loaded line or a bad driver.
- Gaps. A Modbus RTU frame must have no gap longer than 1.5 character times inside the frame, and at least 3.5 character times between frames. At 9 600 baud, that is 1.6 ms and 3.6 ms.
- Collision. Two devices transmitting at the same time show a distorted waveform with a doubled amplitude and some bits wrong: look for two masters, or a slave answering to the wrong address.
Reading a Modbus capture
| Frame | Bytes (hex) | Meaning |
|---|---|---|
| Request | 01 03 00 00 00 02 C4 0B | Slave 01, function 03 (read holding registers), start address 0000, quantity 0002, CRC (low byte first) |
| Response | 01 03 04 00 0A 01 02 5A 60 | Slave 01, function 03, byte count 04, register 0 = 000A (10), register 1 = 0102 (258), CRC |
| Exception | 01 83 02 C0 F1 | Slave 01, function 03 + 80 = 83 (an error), exception code 02 (illegal data address), CRC |
| Exception code | Name | Usual cause |
|---|---|---|
| 01 | Illegal function | The device does not support that function code (reading with 04 when it needs 03, or writing a read-only value) |
| 02 | Illegal data address | The register does not exist: an off-by-one error or the wrong register map |
| 03 | Illegal data value | Quantity too large, or the value is outside the allowed range |
| 04 | Slave device failure | The device had an internal error while carrying out the request |
| 05–06 | Acknowledge / busy | The device is busy; try again later |
| 0A–0B | Gateway path unavailable / target failed to respond | A gateway could not reach the device behind it |
- Request seen, no response. The device did not hear the request (wrong address, baud, polarity) or chose not to answer (CRC error, parity error). Check the settings and the A/B wires.
- Response with an exception. The link works; the problem is the request. Compare the address and function with the register map.
- Response with a bad CRC. Noise, wrong termination, or a data-rate mismatch.
- Garbled bytes with the right pattern. If 01 03 arrives as 80 or FE, the baud rate or bit order is off; if bytes are always doubled or shifted, parity or stop bits are different.
- Two requests and no gap. A master that sends the next request before the slave replied has a timeout that is too short.
- Responses from several devices at once. Two devices share an address.
Symptoms and likely causes
| Symptom | Likely causes | First check |
|---|---|---|
| No bytes at all | Cable open, wrong port, master not polling, A/B not connected | Meter on the line during a poll; loopback test of the PC |
| Request seen, no response | Wrong address, baud or parity; A/B swapped; slave powered off | Compare settings; swap A and B; try another address |
| Garbage characters | Baud rate or data bits mismatch; 7/8 bit; wrong voltage levels | Set the PC to match the device and scan the bauds |
| Works for a while, then stops | Ground loop, noise from a drive, loose terminal, intermittent connector | Look for errors with a scope when it fails; check shields and routing |
| Works with a short cable, not a long one | Missing termination or bias; too high a baud rate | Terminate both ends, add bias, lower the baud rate |
| One device fails, the others work | Wrong address, long stub, bad connector, faulty transceiver | Test it alone with the PC |
| Random CRC errors | Electrical noise, reflections, bad grounding | Scope for ringing; separate the cable from power wiring; use shielded pair |
| Values wrong but communication fine | Off-by-one address, scaling, word order, signed against unsigned | Compare to the device display; check the register map |
| Everything stops when one device is plugged in | A failed driver holding the line, or two masters | Unplug devices one by one until it recovers |
| PLC shows a fault, PC works | PLC port settings or program, timeout too short, wrong protocol selected | Compare the PLC port settings with those that worked on the PC |
Sniffing Ethernet with Wireshark
Wireshark is a free packet analyzer that understands most industrial protocols. Select the network adapter, start the capture, send some data, stop, and read the packets. A capture can be saved and sent to a manufacturer’s support team.
| Protocol | Display filter | What to look for |
|---|---|---|
| Modbus TCP | modbus or tcp.port == 502 | Requests and responses by transaction ID; exception responses; no reply |
| EtherNet/IP and CIP | enip || cip | List Identity replies, connection set-up (Forward Open), and cyclic I/O packets on UDP 2222 |
| Siemens S7 | s7comm or tcp.port == 102 | Read and write requests; set-up communication; errors when PUT/GET is disabled |
| PROFINET | pn_dcp or pn_io | DCP identify requests and replies show device names; cyclic data |
| OPC UA | opcua | Hello, open secure channel, session set-up; security errors |
| Everything to one device | ip.addr == 192.168.1.10 | Whether it answers at all |
| Problems | tcp.analysis.flags | Retransmissions, resets, zero windows |
| Resets and refused connections | tcp.flags.reset == 1 | The server closed the connection or has no service on that port |
| ARP trouble | arp | Requests with no replies mean the device is not on the network or has a different address; duplicate IP warnings |
- Start with ARP and ping. If the PLC does not answer ARP, nothing above it will work. If it answers ARP and ping but not the protocol, look at the port, the protocol settings and any firewall.
- Look at the handshake. A TCP connection starts with SYN, SYN/ACK, ACK. A SYN with no reply means no route or a firewall; a reset after SYN means nothing is listening on the port.
- Time. Set the time column to “since previous displayed packet” to find delays, such as a slow response to a request.
- Wireshark does not need the PLC’s permission, but capturing on a plant network can be restricted. Get approval before connecting a laptop.
Getting the traffic: mirror ports and taps
On a switched network, a laptop plugged into a spare port sees only broadcast traffic and its own. To see another device’s conversation you must have the traffic copied to you.
| Method | How it works | Notes |
|---|---|---|
| Mirror (SPAN) port | A managed switch copies the traffic of one or more ports to a chosen port | Needs a managed switch and permission to change it; can drop packets on a busy link |
| Network tap | A small inline device passes the traffic and copies it to a monitor port | Passive; does not change the switch; the device breaks the link for a moment when installed |
| Hub | An old repeater hub shares everything with every port | Rarely used; limited to 10 Mbit/s; not for modern networks |
| Capture on the PC itself | Wireshark on the engineering laptop sees its own traffic | Enough when the laptop is one of the two ends |
| Packet capture in the device | Some PLCs and switches can capture internally | Check the manufacturer’s tools |
Other network tools
| Tool | Use |
|---|---|
| ping | Is the device reachable? Run a continuous ping while wiggling a cable to find an intermittent connection |
| arp -a | Shows the IP and MAC address pairs the PC knows; a duplicate IP appears as the same MAC for two devices, or a MAC that changes |
| IP scanner (Advanced IP Scanner, Angry IP Scanner, nmap) | Finds the devices on a subnet; use carefully on a live plant network |
| Vendor discovery tools | RSLinx/Studio 5000 browse, TIA Portal accessible devices, PRONETA, BOOTP/DHCP tool: find a device with an unknown address |
| Cable tester | Checks each pair of an RJ45 cable; some measure length |
| Managed switch diagnostics | Port counters (CRC errors, collisions, speed and duplex) show a bad cable or a mismatch |
| Speed and duplex | A port forced to 100 full next to one on auto negotiates down to half duplex and produces errors |
Cautions
- Get permission. Plugging a laptop into a production network or opening a control panel needs approval, and some sites forbid it.
- Never transmit when sniffing. A serial tap that drives the line, or a laptop that sends traffic to a PLC network, can stop a machine.
- Reading is safer than writing. Do not write to registers or tags on a running machine unless you know what they do.
- Isolate. Use an isolated adapter and take care with panel voltages; follow the lockout and arc-flash rules of the plant.
- Remove your test gear. Take out taps, temporary terminators and jumpers when finished, and restore the settings you changed.
- Secure the data. Captures can contain passwords and process data: store and share them with care.
Related
- Industrial Communication: the overview of this guide.
- Connecting PLCs, Drives and HMIs: the set-up that these tools verify.
- Troubleshooting Industrial Networks: the method these tools serve, with symptom tables and case studies.
- Industrial Communication: the protocols in detail.
FAQ
What is the cheapest way to see what is on an RS-485 line?
A USB-RS485 adapter (a few dollars to a few tens) in receive-only mode, plus a terminal or Docklight in hex mode. Set the same baud rate and parity, and the master’s requests and the slaves’ responses both appear.
Can I sniff Modbus RTU while the PLC is connected?
Yes, on an RS-485 bus: attach the adapter in parallel with a short stub. Do not add termination or bias, and do not let the adapter transmit.
Why does Wireshark not show any packets from my PLC?
On a switched network you only see traffic addressed to your own PC. Use a mirror port or a tap, or capture on the PLC’s own engineering computer.
What does a CRC error mean?
The receiver computed a different check value from the one in the frame, so at least one bit changed in transit. It is usually noise or a mismatched baud rate; the device discards the frame and the master sees a timeout.
Do I need a logic analyzer?
Not for most jobs. A USB adapter and a meter solve most serial problems; a scope or logic analyzer helps with timing, noise and signal-quality questions.
References
- Modbus Organization, MODBUS over Serial Line Specification and Implementation Guide V1.02 (frame format, timing, CRC, exception codes).
- TIA/EIA-485-A and TIA/EIA-232-F (electrical characteristics).
- Wireshark Foundation, Wireshark User’s Guide and display filter reference.
- Rockwell Automation, EtherNet/IP Network Troubleshooting notes; PROFIBUS & PROFINET International, PROFINET Commissioning Guideline.
Last reviewed: October 2026. Speeds, lengths, node counts and menu names are typical: confirm against the specification and the manufacturer’s documentation for the devices you use.