AWG Wire Gauge Table
American Wire Gauge 0000 to 40: diameter, area, copper resistance and mass.
American Wire Gauge (AWG) is the wire size system used for electrical conductors in North America. Like sheet gauge, a larger number means a thinner wire, but AWG is a true geometric series: every 6 gauge steps halve the diameter, and every 3 steps halve the area. This table gives the bare copper dimensions and resistance for every size from 0000 (4/0) to 40.
The table
| AWG | Diameter (mm) | Diameter (in) | Area (mm2) | Resistance, copper at 20 C (ohm/km) | Resistance (ohm per 1000 ft) | Copper mass (kg/km) |
|---|---|---|---|---|---|---|
| 0000 (4/0) | 11.684 | 0.46 | 107.219 | 0.161 | 0.049 | 960.685 |
| 000 (3/0) | 10.4049 | 0.40964 | 85.0288 | 0.203 | 0.062 | 761.858 |
| 00 (2/0) | 9.2658 | 0.3648 | 67.4309 | 0.256 | 0.078 | 604.181 |
| 0 (1/0) | 8.2515 | 0.32486 | 53.4751 | 0.322 | 0.098 | 479.137 |
| 1 | 7.3481 | 0.2893 | 42.4077 | 0.407 | 0.124 | 379.973 |
| 2 | 6.5437 | 0.25763 | 33.6308 | 0.513 | 0.156 | 301.332 |
| 3 | 5.8273 | 0.22942 | 26.6705 | 0.646 | 0.197 | 238.967 |
| 4 | 5.1894 | 0.20431 | 21.1506 | 0.815 | 0.248 | 189.51 |
| 5 | 4.6213 | 0.18194 | 16.7732 | 1.028 | 0.313 | 150.288 |
| 6 | 4.1154 | 0.16202 | 13.3018 | 1.296 | 0.395 | 119.184 |
| 7 | 3.6649 | 0.14429 | 10.5488 | 1.634 | 0.498 | 94.517 |
| 8 | 3.2636 | 0.12849 | 8.3656 | 2.061 | 0.628 | 74.955 |
| 9 | 2.9064 | 0.11442 | 6.6342 | 2.599 | 0.792 | 59.442 |
| 10 | 2.5882 | 0.1019 | 5.2612 | 3.277 | 0.999 | 47.14 |
| 11 | 2.3048 | 0.09074 | 4.1723 | 4.132 | 1.26 | 37.384 |
| 12 | 2.0525 | 0.08081 | 3.3088 | 5.211 | 1.588 | 29.647 |
| 13 | 1.8278 | 0.07196 | 2.624 | 6.571 | 2.003 | 23.511 |
| 14 | 1.6277 | 0.06408 | 2.0809 | 8.285 | 2.525 | 18.645 |
| 15 | 1.4495 | 0.05707 | 1.6502 | 10.448 | 3.184 | 14.786 |
| 16 | 1.2908 | 0.05082 | 1.3087 | 13.174 | 4.015 | 11.726 |
| 17 | 1.1495 | 0.04526 | 1.0378 | 16.612 | 5.063 | 9.299 |
| 18 | 1.0237 | 0.0403 | 0.823 | 20.948 | 6.385 | 7.374 |
| 19 | 0.9116 | 0.03589 | 0.6527 | 26.415 | 8.051 | 5.848 |
| 20 | 0.8118 | 0.03196 | 0.5176 | 33.308 | 10.152 | 4.638 |
| 21 | 0.7229 | 0.02846 | 0.4105 | 42.001 | 12.802 | 3.678 |
| 22 | 0.6438 | 0.02535 | 0.3255 | 52.962 | 16.143 | 2.917 |
| 23 | 0.5733 | 0.02257 | 0.2582 | 66.784 | 20.356 | 2.313 |
| 24 | 0.5106 | 0.0201 | 0.2047 | 84.213 | 25.668 | 1.834 |
| 25 | 0.4547 | 0.0179 | 0.1624 | 106.191 | 32.367 | 1.455 |
| 26 | 0.4049 | 0.01594 | 0.1288 | 133.904 | 40.814 | 1.154 |
| 27 | 0.3606 | 0.0142 | 0.1021 | 168.85 | 51.466 | 0.915 |
| 28 | 0.3211 | 0.01264 | 0.081 | 212.916 | 64.897 | 0.726 |
| 29 | 0.2859 | 0.01126 | 0.0642 | 268.482 | 81.833 | 0.575 |
| 30 | 0.2546 | 0.01003 | 0.0509 | 338.55 | 103.19 | 0.456 |
| 31 | 0.2268 | 0.00893 | 0.0404 | 426.904 | 130.12 | 0.362 |
| 32 | 0.2019 | 0.00795 | 0.032 | 538.315 | 164.079 | 0.287 |
| 33 | 0.1798 | 0.00708 | 0.0254 | 678.803 | 206.899 | 0.228 |
| 34 | 0.1601 | 0.0063 | 0.0201 | 855.955 | 260.895 | 0.18 |
| 35 | 0.1426 | 0.00561 | 0.016 | 1079.34 | 328.983 | 0.143 |
| 36 | 0.127 | 0.005 | 0.0127 | 1361.02 | 414.839 | 0.114 |
| 37 | 0.1131 | 0.00445 | 0.01 | 1716.22 | 523.103 | 0.09 |
| 38 | 0.1007 | 0.00397 | 0.008 | 2164.11 | 659.621 | 0.071 |
| 39 | 0.0897 | 0.00353 | 0.0063 | 2728.89 | 831.766 | 0.057 |
| 40 | 0.0799 | 0.00314 | 0.005 | 3441.07 | 1048.84 | 0.045 |
Source and notes: ASTM B258: d = 0.127 mm x 92^((36 - n) / 39). Copper resistivity 1.7241e-8 ohm m, density 8 960 kg/m3.
How to use this table
- Find the AWG number (sizes 0000, 000 and 00 are written 4/0, 3/0 and 2/0).
- Read the diameter for hole and connector sizes and the area for current capacity and voltage drop.
- Use the resistance per kilometer (or per 1 000 ft) for voltage drop and power loss.
Worked example: 14 AWG copper, 25 m run, 15 A load on a 120 V circuit
- 14 AWG is 1.628 mm across with an area of 2.081 mm² and a resistance of 8.285 ohm/km at 20 C.
- The current flows out and back, so the conductor length is 2 × 25 m = 50 m: R = 50 × 8.285 ÷ 1 000 = 0.414 ohm.
- Voltage drop = I × R = 15 × 0.414 = 6.21 V, which is 5.2 percent of 120 V. That is over the 3 percent usually recommended, so a thicker wire (12 AWG) is the better choice.
Notes and cautions
- Current rating (ampacity) depends on the insulation, the installation and the code in force. It is not a property of the gauge alone: use the ampacity tool and the applicable code.
- Resistance rises with temperature, by about 0.39 percent per degree C for copper. The table is for 20 C.
- Stranded wire has slightly more resistance than a solid conductor of the same AWG size because of the lay of the strands.
Related tools and guides
- Wire Ampacity and Voltage Drop Calculator
- Cable Sizing and Voltage Drop (guide)
- Resistivity of Metals and Alloys
- All reference tables
FAQ
What is the diameter of 12 AWG wire?
About 2.05 mm (0.0808 inch) for bare solid copper, with an area of 3.31 mm².
What happens every 6 AWG steps?
The diameter doubles or halves. Every 3 steps the area, and so the weight, doubles or halves, and the resistance does the opposite.
Which AWG for 15 amps?
Common practice in North American building wiring is 14 AWG for 15 A and 12 AWG for 20 A, subject to the code and the installation. See the ampacity tool.
Sources