Pressure, Level and Flow Sensors

Gauge, absolute and differential pressure, level by hydrostatic, ultrasonic and radar methods, and flow by differential pressure, magnetic and vortex meters.

Pressure: types and units

Pressure is force per area. Three kinds are measured: gauge pressure (relative to the atmosphere, the most common), absolute pressure (relative to a perfect vacuum, needed for altitude, vacuum and gas calculations) and differential pressure (between two points, used for flow, filters and level in a closed tank).

Gauge, absolute and differential pressureGauge (barg, psig)diaphragmprocess pressure Popen to the atmosphereAbsolute (bara, psia)diaphragmprocess pressure Psealed vacuum referenceDifferential (bar, kPa)diaphragmpressure P1pressure P2Gauge = absolute − atmosphere (about 1.013 bar). A vented gauge sensor changes with the weather by up to ±0.03 bar if used as absolute.Differential sensors measure flow across an orifice, filter drop and level in a closed tank.
Gauge, absolute and differential pressure.
UnitIn one barNotes
kPa100 kPaSI-derived; 1 Pa = 1 N/m²
psi14.50 psiPounds per square inch; psig is gauge, psia absolute
mmHg (torr)750 mmHgVacuum and medicine
inH2O401.5 inH2OLow pressures and air flow
Atmosphere0.987 atmStandard atmosphere is 1.01325 bar

Pressure sensors and installation

  • Piezoresistive (strain-gauge) sensors bond strain gauges to a steel or silicon diaphragm and measure the bridge output (see Force, Load Cells and Vibration). They are the standard for 0.1 to 1000 bar, with accuracies of 0.1 to 0.5 percent.
  • Capacitive sensors measure the change in capacitance of a diaphragm; they are excellent at low pressures and for differential measurements.
  • Piezoelectric sensors respond only to changes of pressure (dynamic), used for combustion, blast and vibration.
  • Pressure switches give an on/off output at a set pressure with an adjustable hysteresis (see Sensor Basics and Selection).
  • Ratings: the working range, the overpressure (the most that can be applied without a lasting change) and the burst pressure. Choose a range about 1.5 times the maximum working pressure, and an overpressure rating well above any surge or water hammer.
  • Process media: wetted materials must suit the fluid (stainless steel, Hastelloy, ceramic). For viscous, hot, corrosive or hygienic media use a diaphragm seal with a fill fluid, or a flush diaphragm.
  • Install it right: mount above a liquid line so that air bubbles escape, below a gas line so that condensate drains, and with a snubber or a damper if there are pulsations. Keep the impulse line short; trapped air or a plug of solids in the line gives a slow or false reading.
  • Zero and orientation: a sensor can read a small error if mounted in a different orientation from the one it was calibrated in (the weight of the fill fluid); re-zero it after mounting.
  • Temperature: check the compensated temperature range, and use a cooling element (a siphon or a pigtail) for steam.

Level measurement

Level measurement methodsHydrostaticPP = ρ g hUltrasonic / radartime of flight to the surfaceFloatfloat, arm and angle sensorCapacitance probecapacitance rises with level
Four ways of measuring the level in a tank.
MethodPrincipleStrengthsLimits
Hydrostatic (pressure)The pressure at the bottom is ρ g hSimple, robust, cheap; works in many tanksNeeds the density; the tank vent and the temperature matter
Ultrasonic (top-mounted)Time of flight of sound to the surfaceNon-contact, no moving partsFoam, vapor, dust, a blocked path, the dead zone, and the temperature (see Proximity Sensors)
Radar (free-space, 26 or 80 GHz)Time of flight of a microwave pulseNot affected by temperature, vapor or pressure, very accurateCostlier; needs a clear beam path; low-reflection liquids
Guided-wave radarA pulse travels down a probe to the liquidWorks in vessels with internals, foam and interfacesBuild-up on the probe; the length of the probe
Float and magnetic floatA float rises with the liquid, with a magnet or a leverSimple, reliable, switches or continuousMoving parts, sticking with sludge
Capacitance probeThe capacitance between the probe and the tank changes with the levelNo moving parts, continuous or pointNeeds a stable dielectric; build-up
Vibrating fork (point level)A tuning fork stops vibrating when coveredIndependent of density, foam, build-upPoint level only
Load cells on the tankWeigh the tank and compute the levelWorks for any tank, includes the contents’ massNeeds a free-standing tank; the piping loads the cells
Optical and conductive probesDetect the liquid at the probe tipCheap point-level switchesLimited to clean or conductive liquids

Hydrostatic level from pressure

The pressure at the bottom of a liquid column is P = ρ × g × h, with ρ the density (kg/m³), g = 9.81 m/s² and h the height (m), in pascals. A pressure transmitter at the bottom of an open tank gives the level directly; in a closed tank a differential sensor subtracts the pressure above the liquid.

Worked example: a 3 m water tank

  • Water (ρ = 1 000 kg/m³) at h = 3.0 m: P = 1 000 × 9.81 × 3.0 = 29 430 Pa = 29.4 kPa = 0.294 bar. A 0 to 0.5 bar sensor suits it, using 59 percent of the range.
  • Resolution: 0.1 percent of the 0.5 bar range is 0.001 bar, equal to 5 mm of water: a 3 m tank is measured to about 5 mm.
  • A different liquid: an oil of density 850 kg/m³ gives only 25.0 kPa at the same height. If the transmitter is calibrated for water, the reading is wrong by the density ratio: the same pressure from water of 3 m means 3.53 m of oil. Always set the density.
  • Temperature changes the density (about 0.02 percent per °C for water near room temperature) and the level reading with it, which matters for tank gauging and custody transfer.
  • Closed pressurized tank: use a differential-pressure transmitter, with the low side connected to the tank top (a dry leg, or a wet leg filled with a reference fluid, with the range suppressed or elevated accordingly).

Worked example: an ultrasonic level sensor

An ultrasonic sensor mounted at the top of a 4.0 m tank measures the distance to the surface: 1.2 m. The level is 4.0 − 1.2 = 2.8 m. The sensor’s blind distance (for example 0.35 m) means the tank cannot be filled above 3.65 m as measured by it: mount it high enough, and set the high-level alarm with a separate switch.

Choosing a level sensor

SituationGood choiceWhy
Clean water, an open tank, low costSubmersible or bottom-mounted pressure sensorSimple and stable
Foaming, steam or vapor above the liquidGuided-wave radar or a pressure sensorUnaffected by the layer above
Corrosive or hygienicRadar (non-contact) or a flush diaphragm sensorNo dead space to clean
Solids and powdersRadar, ultrasonic, or load cellsContinuous measurement of the pile
A simple high or low alarmA float, fork or capacitive switchCheap and reliable
A very accurate measurement (custody transfer)High-accuracy radar or servo gaugesAccuracy of 1 mm or better

Flow measurement

Flow is measured as a volume flow (m³/h, L/min) or a mass flow (kg/h). A volume flow is the flow velocity times the area of the pipe, Q = A × v; the mass flow multiplies by the density.

TypePrincipleStrengthsLimits
Differential pressure (orifice, venturi, pitot)A constriction creates a pressure drop proportional to the square of the flowWell established, no moving parts, any clean fluidPressure loss; the square-root relation limits the turndown (about 3:1 to 5:1)
Magnetic (electromagnetic)A conductive liquid moving through a magnetic field induces a voltage proportional to the velocityNo obstruction, wide range, any conductive liquid, slurriesLiquid must be conductive (above about 5 µS/cm); not for gas or oil
VortexA bluff body sheds vortices at a frequency proportional to the velocitySteam, gas and liquid; no moving partsNeeds a minimum velocity; sensitive to vibration
CoriolisVibrating tubes twist in proportion to the mass flowDirect mass flow and density, very accurateCostly; pressure drop; large sizes are heavy
Ultrasonic (transit time or Doppler)Sound travels faster with the flow than against itClamp-on, no contact with the fluidNeeds a clean, uniform pipe wall; accuracy lower
TurbineA rotor’s speed is proportional to the flowAccurate, fast, cheap for clean liquidsMoving parts, bearings, wear
Thermal massA heated element cooled by the gas flowDirect mass flow of gases, low flowsGas composition affects it
Positive displacementFixed volumes counted by gears or pistonsViscous liquids, accurate at low flowPressure drop, wear

Worked example: three flow calculations

  • Differential pressure. Flow is proportional to √ΔP. If an orifice gives 25 kPa at full flow, at 50 percent flow the ΔP is only 25 percent of that: 6.25 kPa. At 20.0 percent of full flow the ΔP is just 1 kPa, below the sensor’s resolution: this is why a DP flowmeter works well only above about 30 percent of its range.
  • Magnetic flowmeter. Water at 2.0 m/s in a DN50 pipe (inside diameter 50 mm): A = π × 0.05² ÷ 4 = 19.63 cm², so Q = A × v = 14.1 m³/h (236 L/min). The voltage is E = B × D × v = 0.01 T × 0.05 m × 2.0 m/s = 1.0 mV: small, hence the shielded cable and the sensor’s dedicated electronics.
  • Vortex. The shedding frequency is f = St × v ÷ d with St ≈ 0.2 and a bluff body d = 15 mm: at 2.0 m/s f = 0.2 × 2.0 ÷ 0.015 = 26.7 Hz. The count of pulses is proportional to the volume that passed.
  • Straight pipe: most meters need a straight length before and after (typically 10 pipe diameters upstream and 5 downstream for a DP or vortex meter, less for a magnetic meter) to give a regular velocity profile.
  • Full pipe: a magnetic, ultrasonic or Coriolis meter must be full of liquid; install it in a rising section or a low point, never at the top of a pipe where air collects.
  • Temperature and pressure compensation convert a volume flow of gas to a standard volume or a mass flow.
  • Totalisers and outputs: 4 to 20 mA, pulse, HART or a fieldbus; the transmitter also shows the total.

Choosing a flowmeter

FluidGood choices
Clean water, conductive liquids, slurriesMagnetic; ultrasonic for a retrofit
Steam and gasVortex, DP with temperature and pressure compensation, thermal mass (gas)
Oil and non-conductive liquidsCoriolis, turbine, positive displacement
Very accurate mass flow, density, concentrationCoriolis
Low-cost indication or checkA rotameter (variable-area flow tube) or a paddlewheel
Open channelsA flume or weir with an ultrasonic level sensor

Troubleshooting

SymptomLikely causeCheck
Pressure reading drifts or is wrong at zeroZero shift (orientation, temperature, overpressure damage)Vent to atmosphere and re-zero; compare with a calibrator
Noisy or oscillating pressurePump pulsations, water hammer, a long impulse lineA snubber, a damping setting, a shorter line
Slow responseA blocked or air-filled impulse line, a thick fill fluidFlush and vent the line
Level reading wrong when the liquid changesThe density setting, temperatureSet the density; compensate for temperature
Ultrasonic level jumpsFoam, an agitator, an obstruction in the beam, a vaporMove or shield the sensor; try radar
Flow reads high or lowAir in the pipe, partly filled pipe, no straight run, a wrong pipe size enteredFull-pipe check, upstream disturbances, parameters
Magnetic meter erraticPoor grounding of the liquid, a low conductivity, electrode foulingGrounding rings, conductivity, clean the electrodes
No flow signalA dry pipe, a fouled sensor, a wiring faultPipe full? The sensor and wires

Related

FAQ

What range of pressure sensor should I buy?

About 1.5 times the maximum working pressure, but not much more: the accuracy is a percentage of the full range, so an oversized sensor reads poorly at the normal pressure. Check the overpressure rating against any surges.

Do I need to know the liquid density for a hydrostatic level?

Yes. The pressure depends on the density, so the level reading is only as good as the density you enter, and it changes with temperature and with the product.

Why does my magnetic flowmeter need grounding?

The signal is a few millivolts. The liquid must be connected to the meter’s reference through the grounding rings or electrodes, or electrical noise and stray currents corrupt the reading.

Can I fit a flowmeter anywhere in the pipe?

No: it needs the right straight run, a full pipe and the right orientation. The data sheet’s installation drawing is as important as its specification.

References

  • ISA, Instrument Engineers’ Handbook, vol. 1: Process Measurement and Analysis, CRC Press.
  • Miller, R. W., Flow Measurement Engineering Handbook, McGraw-Hill; ISO 5167 (differential pressure flowmeters).
  • Endress+Hauser, Emerson (Rosemount), Siemens and VEGA application guides for pressure, level and flow.

Last reviewed: October 2026. Formulas and figures are typical; use the manufacturer’s data and the applicable standards for real installations.