Heating and Cooling Load Calculations

Heat loss, solar and internal gains, ventilation load and the sensible and latent split, worked for a 100 square meter office.

Why calculate loads

The load is the heat that must be added or removed to hold the room at its set conditions. Equipment is chosen from it: an oversized chiller or furnace costs more, runs in short cycles, controls humidity poorly and wears out sooner; an undersized one fails on the hottest or coldest day. The calculation has two halves with different worst cases: heating (the coldest night, no sun, no internal gains) and cooling (a hot afternoon with the sun on the glass and the room full).

The heating load

It is the sum of the heat lost by conduction through each part of the envelope and by air leaving the building:

Q = Σ U A ΔT + 1.2 × V̇ × ΔT    (V̇ in L/s gives W)

Ventilation and infiltration usually make up a third to a half of the load in a modern building. Add a pick-up allowance for warming the structure after a night setback. Ignore internal gains and sun (they may not be there when it is coldest). Better windows lower the load: replacing the 12 m² of U = 2.8 glazing with U = 1.4 cuts the glass loss at 26 K from 874 W to 437 W.

The cooling load: sources of heat

SourceHow to calculate itSensible or latent
Conduction through walls and roofU A ΔTeq; the equivalent temperature difference includes sun and heat storage (the wall delays and smooths the peak)sensible
Conduction through glassU A (Tout − Tin)sensible
Solar through glassA × SHGC × solar irradiance (W/m², from the orientation and hour); shading and film lower SHGCsensible
Peopleabout 75 W sensible and 55 W latent each in an office; more with activityboth
Lightsinstalled W/m² × area (LED: 5 to 10 W/m²)sensible
Equipmentactual measured use, not nameplate (a computer draws 30 to 100 W, not its 300 W rating)sensible (latent for kitchens)
Ventilation air1.2 × flow × ΔT; 2 501 × ṁ × ΔW for the latent partboth
Infiltrationair changes per hour × volume, then as ventilationboth

Heat does not all become cooling load at once: solar and lighting heat warms the surfaces first (radiant part), which then release it to the air later. Detailed methods (the ASHRAE heat balance and radiant time series methods, CIBSE admittance) account for this delay; the simple steady-state estimate used here gives a safe upper figure for a light building.

Worked example: the 100 m² office

Worked example: peak cooling load at 33 °C outdoors

Office of 10 m × 10 m × 3 m: 40 m² of sunlit wall (U = 0.321, ΔTeq = 12 K), 12 m² of glass (U = 2.8, SHGC 0.4, peak solar 550 W/m²), ten people, 10 W/m² of lighting, 8 W/m² of equipment. Outdoor design 33 °C and 40 percent; indoor 24 °C and 50 percent; outdoor air 10 × 2.5 + 0.3 × 100 = 55 L/s.

SourceCalculationSensible (W)Latent (W)
Wall conduction0.321 × 40 × 12154—
Glass conduction2.8 × 12 × (33 − 24)302—
Solar through glass12 × 0.4 × 5502 640—
People10 × 75 and 10 × 55750550
Lighting10 W/m² × 100 m²1 000—
Equipment8 W/m² × 100 m²800—
Room load5 646550
Ventilation air1.2 × 55 × 9 and ṁ ΔW hfg563515
Coil load6 2091 065
  • Total 7.27 kW (2.07 tons), which is 73 W/m². Solar gain through the glass alone is 36 percent of it.
  • Room sensible heat ratio = 5 646 ÷ (5 646 + 550) = 0.91; with the ventilation air the coil SHR is 0.85.
  • Supply air at 13 °C (11 K below the room): flow = 5 646 ÷ (1.2 × 1.006 × 11) = 425 L/s (901 cfm), about 4.3 L/s per m² of floor.
  • External shading that drops the SHGC from 0.4 to 0.25 saves 990 W (14 percent of the total).
  • Infiltration at 0.3 air changes an hour adds another 25 L/s and about 272 W sensible: keep the building pressurized and the envelope tight.
Peak cooling load of the example office, by sourceSolar through glass2 640 WLighting1 000 WEquipment800 WPeople (sensible)750 WVentilation air (sensible)563 WVentilation air (latent)515 WPeople (latent)550 WGlass conduction302 WWall conduction154 WTotal 7.27 kW: sensible 6.21 kW and latent 1.06 kW. Blue bars are latent load; gray and orange bars are sensible.
The peak cooling load of the example office, by source. Cutting the solar gain is the biggest single lever.

Sensible and latent: the heat ratio

Cooling equipment is chosen for both parts. The room SHR sets the supply air condition: a room SHR of 0.91 can be handled by a coil that dehumidifies only a little; a lecture hall or restaurant with an SHR of 0.7 needs a much colder coil, or a separate dehumidifier. If the coil only handles the sensible load the humidity creeps up; this is the commonest cause of a clammy, cold room in humid climates (see Psychrometric Processes).

Sizing and safety factors

The peak of every load never happens at once (the sun is on the west glass in the afternoon but the east glass in the morning), so a building’s block load is less than the sum of the room peaks: a diversity of 0.8 to 0.9 for people and equipment. A 5 to 15 percent margin is then added. For the office: 7.27 kW × 0.85 × 1.10 = 6.80 kW. Piling on a 30 or 50 percent “just in case” margin on top of the loads is the common way equipment ends up oversized (and poor at part load).

Rules of thumb and their limits

BuildingCooling (W/m²)Heating (W/m²)
Office (modern, good envelope)70 to 10030 to 60
Office (older, glazed)100 to 15060 to 100
Retail100 to 15040 to 80
School classroom90 to 13050 to 90
Dwelling (cold climate)30 to 7050 to 100

Rules of thumb are good for a first estimate and for checking a calculation (the example office is 73 W/m²), but they hide glazing, orientation, occupancy and climate. Always do the calculation before selecting equipment.

Related

FAQ

What is SHGC?

Solar heat gain coefficient: the fraction of the incident solar energy that enters through the glass as heat. Clear double glazing is about 0.7, low-e glass 0.25 to 0.4.

Do I include the sun in the heating load?

No. The design condition is a cold night; the sun may be gone.

Why is the cooling load not just U A ΔT?

Because the sun and the stored heat in the structure add much more than the air-to-air difference.

What is a block load?

The peak of the whole building at once, which is smaller than the sum of the room peaks because they peak at different hours.

References

  • ASHRAE, Handbook – Fundamentals, Chapters 17 and 18 (nonresidential and residential heating and cooling load calculations); CIBSE Guide A and Guide J (weather and solar data).
  • EN 12831 (heating load) and ISO 52016 (energy needs for heating and cooling).
  • Spitler, J. D., Load Calculation Applications Manual, ASHRAE.

Last reviewed: October 2026. Design values are examples; use local weather data and the applicable code.