Electrical Safety, Testing and Troubleshooting
Shock and arc-flash hazards, lockout, insulation and earth tests, motor and cable faults and a troubleshooting table.
The hazards
Electricity kills in three ways: by passing current through the body (shock), by the intense heat and blast of an arc, and by fire from overheated conductors and connections. Each is controlled by a hierarchy: eliminate the hazard (work dead), engineer it out (insulation, guards, protection, see Protection, Earthing and RCDs), apply procedures (lockout, permits) and, last, use personal protective equipment. This page is general information, not a replacement for training and the standards that apply to your work: electrical work must be done by competent people.
Electric shock
| Current through the body (50 Hz) | Effect |
|---|---|
| about 0.5 to 1 mA | threshold of perception |
| 5 to 10 mA | painful; at about 10 mA the muscles may not let go |
| 30 mA | breathing difficult; the limit an RCD protects against |
| 50 to 100 mA or more for a fraction of a second | ventricular fibrillation, usually fatal without a defibrillator |
| amperes | burns, tissue damage, cardiac arrest |
The severity depends on the current and the time, with the fibrillation limit about I = 116 ÷ √t mA (Dalziel): 580 mA for 40 ms (an RCD), 183 mA for 0.4 s (a breaker), 52 mA for 5 s. The body’s resistance varies from about 1 000 Ω (wet skin, a good contact) to 100 000 Ω (dry, a poor contact), so the current from 230 V can be 2 to 230 mA. Treat any voltage above 50 V AC (120 V DC) as dangerous, and any wet place as worse. A person who has been shocked should be seen by a doctor, even if they feel well, because heart rhythm problems can appear later.
Arc flash and arc blast
A short circuit through the air makes an arc at 10 000 to 20 000 K that vaporizes the copper, expands it by a factor of 67 000, and releases an enormous heat and pressure wave. The hazard is the incident energy at the working distance, in cal/cm² (1.2 cal/cm² causes a second-degree burn on bare skin in a fraction of a second). IEEE 1584 gives the full method; the old Ralph Lee equation E = 2.142 × 10⁶ V Ibf t ÷ D² (J/cm², V in kV, current in kA, t in s, D in mm) gives an estimate for a quick view of the factors:
Worked example: the 100 kVA transformer board
- Fault current at the board 3 608 A (Transformers and Distribution), 400 V, working distance 450 mm, cleared in 0.1 s: E = 1.53 J/cm² = 0.36 cal/cm²: below the burn threshold.
- If the protection were slow and took 1 s: E = 3.6 cal/cm², 10 times more, in the range where flame-resistant clothing is needed. The energy is proportional to the clearing time, which is why a fast breaker and a short time delay on the main matter so much.
- At twice the distance (900 mm, 0.1 s): 0.09 cal/cm², a quarter, because the energy falls as D².
- Reduce the hazard by faster protection (current-limiting fuses, arc-flash relays), maintenance mode settings, remote racking, lower fault levels and working de-energized. The result is shown on an arc-flash label (NFPA 70E, IEEE 1584).
Safe working: isolate, lock out, prove dead
- Plan: identify every source of energy (including a second feed, back-feed from a generator or solar array, capacitors, stored mechanical energy, hydraulic accumulators).
- Isolate: open the isolator and the switch the correct way; check it visually where possible.
- Lock out and tag: each worker puts a personal lock on the isolator; no lock, no work. Keep the key.
- Prove dead: with a tester that you have proved on a known live source, test every conductor to earth and to each other, then re-prove the tester on the known source (the three-point test).
- Discharge and earth: capacitors and drives hold a charge for minutes (read the label); apply earths where a back-feed is possible.
- Live work only when dead work is impossible, with a permit, trained people, insulated tools, the right PPE and a second person who knows how to cut the power and give first aid.
Testing: insulation, earth and continuity
| Test | Instrument and voltage | What it checks | Pass guide (typical) |
|---|---|---|---|
| Insulation resistance | insulation tester, 500 V (1 000 V for 690 V circuits) | leakage through insulation between conductors and to earth | ≥ 1 MΩ for installations; motors ≥ (rated kV + 1) MΩ, much more when new |
| Polarization index | insulation tester, 10 minute test | dryness and aging of a motor or cable | ratio of the 10-minute to the 1-minute reading ≥ 2 |
| Continuity of protective conductors | low-resistance ohmmeter, 200 mA | unbroken earth paths | a few milliohms per conductor, agree with the calculation |
| Earth-fault loop impedance | loop tester | Zs low enough to trip the device quickly | below the tabulated maximum (see Protection, Earthing and RCDs) |
| RCD trip time and current | RCD tester | trip at 30 mA and within 40 ms at 5 × IΔn | per the standard |
| Earth electrode resistance | earth tester (fall-of-potential) | quality of the electrode | depends on the system; as low as practical |
Worked example: testing and diagnosing the press motor
Worked example: five readings
- Insulation: the 400 V motor needs at least (0.4 + 1) = 1.4 MΩ. A reading of 5.0 MΩ at a winding temperature of 40 °C corresponds to about 20 MΩ at 20 °C (resistance halves for every 10 K rise), so it is healthy. A reading of 2.0 MΩ at 40 °C would be 8 MΩ at 20 °C: acceptable, but trend it, and a polarization index of 2.0 (2.4 MΩ at 10 min ÷ 1.2 MΩ at 1 min) shows a dry winding.
- Single phasing: if one phase is lost under load the motor keeps running on two, drawing about √3 × 20.5 = 35.6 A (a 73 percent rise), overheating the windings quickly; clamp-meter readings of one line at zero and the others high point to a blown fuse, a failed contact or a loose terminal.
- Voltage unbalance: line voltages 410, 400 and 390 V: the average is 400 V and the maximum deviation 10 V = 2.5 percent. The current unbalance is about 6 to 10 times the voltage unbalance, so some 15 percent (or more); the motor needs derating above 1 percent unbalance.
- A loose terminal: a connection of only 5 mΩ (a loose lug) at 20.5 A dissipates I² R = 2.1 W in a few cubic centimeters: red-hot in minutes. Torque-check terminals, and look for discolored insulation.
- Earth electrode: a 2.4 m rod in soil of 100 Ω·m has a resistance of about ρ ÷ (2πL) × (ln(4L ÷ d) − 1) = 36 Ω: useless on its own for a TN system (use the supply’s return path) but a typical local supplement.
Troubleshooting
| Symptom | Likely causes | Check |
|---|---|---|
| Motor does not start, hums | single phase (lost fuse), jammed load, broken rotor bars, low voltage | voltage on all three lines at the motor; shaft turns by hand |
| Trips on start | breaker too small or wrong curve; starting current too high; overload set too low | peak starting current against the magnetic trip; relay class |
| Trips after a time running | overload (mechanical), high ambient, blocked ventilation, voltage unbalance, worn bearings | running current against the nameplate; temperatures; unbalance |
| RCD trips | leakage: damp equipment, drive filters, insulation damage | isolate circuits; measure leakage with a clamp meter; insulation test |
| Motor overheats | overload, poor cooling, too many starts, low voltage, harmonic heating on a drive | current, airflow, duty cycle, supply quality |
| Lights flicker or dim when a motor starts | high starting current and a weak supply or long cable | voltage dip at the load; soft start or a larger cable (Cable Sizing and Voltage Drop) |
| Burning smell, discolored terminal | loose connection, undersized cable, an overloaded circuit | isolate; thermal image; torque the terminals; inspect |
| Tingling from metalwork | earth fault or a poor protective conductor; stray leakage | isolate at once; test continuity and loop impedance |
| Neutral hot or overloaded | unbalanced single-phase loads or triplen harmonics | neutral current with a true-RMS clamp (Power Factor, Harmonics and Energy) |
Thermography and maintenance
A thermal camera finds loose connections, overloaded phases and failing bearings before they fail: a joint 10 to 15 K hotter than the same joint on the other phases under load is a warning, and over 40 K an urgent job. Scan panels yearly under load. Maintenance includes cleaning and tightening, checking protection settings and breaker operation, testing RCDs and earth continuity, insulation tests on motors and cables, battery and UPS checks, and keeping accurate drawings and labels. Record every reading: the trend tells more than a single value.
Related
- Previous: Solar PV, Batteries and Backup Power. Back to the overview: Electrical Power.
- Workshop Safety for the wider safety guide.
- Protection, Earthing and RCDs for breakers, RCDs and earthing.
FAQ
Is a 12 V supply safe to touch?
Normally yes: below about 50 V the current through the skin is small. But batteries can deliver huge short-circuit currents that melt tools and burn, and arcs at 24 V DC and above can be hazardous.
What should I do if someone is stuck to a live conductor?
Switch off the supply if you can reach the switch safely. Otherwise push them clear with a dry non-conductive object. Call for help, start CPR if there is no breathing, and use an AED.
Can I trust a non-contact voltage tester?
It is a useful first check, not proof of dead: use a proved two-pole tester. Shielded and low-voltage cables can mislead it.
How often should installations be tested?
Fixed installations typically every 5 years (1 to 3 for harsh or commercial sites); portable tools and RCDs more often. Follow the local code and the risk assessment.
References
- NFPA 70E (electrical safety in the workplace), IEEE 1584 (arc-flash hazard calculations), IEC 60479-1 (effects of current on human beings), IEC 61557 (test equipment), EN 50110 (operation of electrical installations).
- IEC 60364-6 (verification) and BS 7671 (inspection and testing); IEEE Std 43 (insulation resistance testing of rotating machinery).
- Cadick, J., Capelli-Schellpfeffer, M., Neitzel, D., Al-Hamdi, A., Electrical Safety Handbook, McGraw-Hill; HSE (UK) guidance note GS38.
Last reviewed: October 2026. This page is general information, not professional safety advice; incident-energy figures use a simplified formula.
