Hazen-Williams Equation
Hazen-Williams equation for the head loss of water in a pipe: h = 10.67 L Q^1.852 / (C^1.852 D^4.87). Enter the flow, length, diameter and roughness coefficient C.
How it works
The Hazen-Williams equation is an empirical formula for the friction loss of water in a pipe. It is quick to use in water supply, sprinkler and irrigation design because the roughness is a single coefficient C and no friction factor iteration is needed.
hf = 10.67 × L × Q1.852 ÷ (C1.852 × D4.8704)
(SI: Q in m³/s, D and L in m)
| Symbol | Meaning | SI unit |
|---|---|---|
| h_f | Head loss | m |
| L | Pipe length | m |
| Q | Flow rate | m³/s |
| C | Hazen-Williams roughness coefficient | – |
| D | Inside diameter | m |
Typical C values: new plastic (PVC, PE) 150, new copper 140 to 150, new cast or ductile iron 130, old cast iron 100, galvanized steel 120, concrete 120. Higher C is smoother. The equation is valid for water at about 5 to 25 °C with velocities up to about 3 m/s and turbulent flow; it should not be used for other fluids or for hot water. Pressure drop follows from Δp = ρ g hf.
Related: Fluid Mechanics and Pipe Flow guide, Darcy-Weisbach equation. All formulas are listed in the Formulas library.
Worked example
10 L/s of water through 100 m of 100 mm pipe with C = 130: the velocity is 1.27 m/s and the head loss is 1.90 m, a pressure drop of 18.6 kPa.
Because the exponent on D is 4.87, going from 100 mm to 125 mm pipe cuts the loss by a factor of about 3.0.
Things to know
The formula is for water only. For oil, air or hot water use the Darcy-Weisbach equation.
C declines with age as pipes corrode and scale: design with the value for old pipe if the system must last decades.
US versions use the same formula with different constants (4.52 L Q^1.85 ÷ (C^1.85 d^4.87) for psi per foot, Q in gpm and d in inches); the calculator converts units so you can use either.
Common questions
What is the Hazen-Williams formula?
In SI units h = 10.67 L Q^1.852 ÷ (C^1.852 D^4.8704), with the head loss h and the length L and diameter D in meters and the flow Q in m³/s.
What is the C factor in Hazen-Williams?
The roughness coefficient: about 150 for smooth plastic, 130 for new iron, 100 for old pipe. A larger C means less friction.
When should you not use Hazen-Williams?
For fluids other than water near room temperature, for laminar flow, for very small pipes (under 50 mm) or for very high velocities. Use Darcy-Weisbach instead.
How do you convert head loss to pressure?
Multiply by the fluid density and gravity: Δp = ρ g h. For water, 1 m of head is 9.79 kPa, and 1 ft of head is 0.433 psi.