Conduction, Convection and Radiation Heat Transfer Calculator
Calculate the heat flow through a composite wall (up to three layers with surface films), by convection from a surface, or by radiation between a surface and its surroundings.
How it works
The three modes of heat transfer have simple rate equations. Pick conduction through a layered wall (with the surface films and the overall U-value), convection from a surface to a fluid, or radiation to the surroundings.
Wall: Q = A ΔT ÷ R″ with R″ = 1/hi + Σ L ÷ k + 1/ho
Convection: Q = h A ΔT
Radiation: Q = ε σ A (Ts⁴ − Tsur⁴)
| Symbol | Meaning | Unit |
|---|---|---|
| Q | Heat flow rate | W |
| A | Area | m² |
| R″ | Thermal resistance per unit area of the whole wall | m²·K/W |
| U | Overall heat transfer coefficient, 1 ÷ R″ | W/(m²·K) |
| k, L | Thermal conductivity and thickness of a layer | W/(m·K), m |
| h | Convective heat transfer coefficient | W/(m²·K) |
| ε, σ | Emissivity and the Stefan-Boltzmann constant | –, W/(m²·K⁴) |
For the wall, the layers and the surface films are in series: add their resistances. A layer left at zero thickness is ignored. Typical film coefficients: indoor surfaces 8, outdoor surfaces 25 (windy) W/(m²·K). The interface temperatures follow from the heat flux and the resistance to each point. Convection and radiation from a hot surface act in parallel and add; see the Heat Transfer guide for combined coefficients.
Related: Heat Transfer guide, Fourier’s law, Convection formula, Stefan-Boltzmann law.
Worked example
A 10 m² wall of 100 mm brick (k = 0.72), 50 mm insulation (k = 0.04) and 12.5 mm plasterboard (k = 0.17), with 20 °C inside (film 8 W/(m²·K)) and −5 °C outside (film 25): R″ = 0.125 + 0.139 + 1.25 + 0.0735 + 0.04 = 1.627 m²·K/W, so U = 0.614 W/(m²·K) and Q = 0.6145 × 10 × 25 = 154 W.
The inside surface sits at 18.1 °C and the outside surface at -4.4 °C. The insulation is only 50 mm thick but supplies 77 percent of the resistance.
Things to know
Use surface temperatures for conduction through a single layer, or the air temperatures with film coefficients (as the wall mode does).
Air gaps, thermal bridges (studs, fasteners) and moisture change the real heat loss; add 10 to 30 percent to a clean-wall result for a real building.
For radiation use absolute temperatures; the calculator converts. Emissivity depends on the surface: polished metal 0.05, painted surfaces 0.9.
Another worked example: convection and radiation together
A painted steel panel of 1 m² sits at 80 °C in a 20 °C room. With a natural-convection coefficient of 8 W/(m²·K), convection removes Q = h A ΔT = 8 × 1 × 60 = 480 W.
Radiation needs absolute temperatures: 353.15 K and 293.15 K. With an emissivity of 0.9 (most paints, whatever the color), Q = 0.9 × 5.670 × 10⁻⁸ × 1 × (353.15⁴ − 293.15⁴) = 417 W. The total is 897 W, and radiation is 46 percent of it. If the same panel were polished aluminum (ε about 0.1) it would radiate only 46 W. At moderate temperatures in still air, radiation is rarely negligible, and the surface finish matters as much as the airflow.
Typical convection coefficients
| Situation | h in W/(m²·K) |
|---|---|
| Free (natural) convection in air and other gases | 2 to 25 |
| Forced convection in air and other gases | 25 to 250 |
| Free convection in water and other liquids | 50 to 1 000 |
| Forced convection in water and other liquids | 100 to 20 000 |
| Boiling and condensation | 2 500 to 100 000 |
Order-of-magnitude ranges from standard heat-transfer texts (Incropera and DeWitt). For design, calculate h from a correlation for the actual shape, fluid and velocity, as explained in the Heat Transfer guide.
Common mistakes
- Using °C in the radiation formula. The fourth-power law needs kelvin. For conduction and convection only the difference matters, so °C is fine there.
- Mixing up U and R. U is the reciprocal of the total resistance: U = 1 ÷ R. A high R is good insulation; a high U is poor insulation.
- Entering thickness in millimeters. L ÷ k needs meters: 50 mm is 0.050 m.
- Mixing SI and US R-values. A US R-value (ft²·°F·h/Btu) is 5.678 times the SI value (m²·K/W). R-13 batt insulation is RSI 2.3.
Common questions
How do you calculate heat transfer through a wall?
Add the resistances of every layer and the two surface films: R″ = 1/hi + ΣL/k + 1/ho. The heat flow is Q = A ΔT ÷ R″, and U = 1/R″ is the U-value.
What are the three modes of heat transfer?
Conduction (through solids), convection (to a moving fluid) and radiation (by electromagnetic waves, needing no medium).
What is a U-value?
The overall heat transfer coefficient of a building element in W/(m²·K): heat flow per square meter per kelvin of temperature difference. Lower is better insulated.
What is the R-value?
The thermal resistance, R = 1/U. In US units R is in ft²·°F·h/BTU: R-1 = 0.176 m²·K/W, so R-20 is 3.52 m²·K/W.
How do I convert between US and SI R-values?
Divide the US R-value by 5.678 to get m²·K/W, or multiply the SI value by 5.678 to get the US one. For U-values the factor works the other way: 1 Btu/(h·ft²·°F) = 5.678 W/(m²·K).
Does doubling the insulation halve the heat loss?
Nearly, but not quite. It doubles the resistance of that layer, while the other layers and the surface films stay the same. And each added layer saves less than the one before, so there is an economic thickness beyond which more insulation does not pay back.
When can I ignore radiation?
When the surface is close to the temperature of its surroundings, when the surface is shiny bare metal, or when forced convection is strong. For painted or oxidized surfaces cooling in still air it is typically a third to a half of the total and should be included.
Sources
- Incropera, F. P. et al., Fundamentals of Heat and Mass Transfer, Wiley.
- ASHRAE Handbook, Fundamentals: heat transfer and building envelope.