Dew Point Calculator

Find the dew point from air temperature and relative humidity, or the relative humidity from the dew point, in °C or °F, with vapor pressure and humidity ratio.

How it works

The dew point is the temperature to which air must be cooled, at constant pressure and moisture content, before water vapor starts to condense. It is a direct measure of how much water the air holds, which relative humidity is not: relative humidity changes whenever the temperature changes, but the dew point stays the same until water is added or removed.

Enter the air temperature and either the relative humidity or the dew point. The calculator finds the water vapor pressure and then the temperature at which that vapor pressure equals the saturation pressure of water.

pw = RH × pws(T) and pws(Td) = pw

pws is the saturation vapor pressure of water (Hyland–Wexler equation, as in the ASHRAE Handbook), RH the relative humidity as a fraction, T the air temperature and Td the dew point. The page solves for Td numerically.

For a quick hand estimate when the relative humidity is above about 50 percent, Td ≈ T − (100 − RH) ÷ 5 with temperatures in °C. At 25 °C and 50 % RH it gives 15 °C, against the exact 13.9 °C: good for a rough check, not for design.

Dew point (°C) for common conditions

Air temperature30 % RH40 % RH50 % RH60 % RH70 % RH80 % RH90 % RH
0 °C (32 °F)-13.9-10.7-8.2-6.1-4.3-2.7-1.3
5 °C (41 °F)-9.9-6.6-4.0-1.90.01.83.5
10 °C (50 °F)-6.0-2.60.12.64.86.78.4
15 °C (59 °F)-2.11.54.77.39.611.613.4
20 °C (68 °F)1.96.09.312.014.416.418.3
25 °C (77 °F)6.210.513.916.719.121.323.2
30 °C (86 °F)10.514.918.421.423.926.228.2
35 °C (95 °F)14.819.423.026.128.731.033.1
40 °C (104 °F)19.123.827.630.733.535.938.0

See also the Psychrometric Calculator and Chart, which adds wet-bulb temperature, enthalpy and specific volume.

Worked example

Air at 25 °C and 50 % relative humidity at sea level. The saturation pressure at 25 °C is 3,169 Pa, so the vapor pressure is pw = 0.5 × 3,169 = 1,585 Pa. The saturation pressure equals that value at 13.86 °C, so the dew point is 13.9 °C (57.0 °F). The humidity ratio is 9.88 g per kg of dry air and the air holds 11.5 g of water per m³.

A cold-water pipe, window or duct surface below 13.9 °C will therefore sweat in that room, while one at 16 °C stays dry.

Things to know

Condensation forms on any surface colder than the dew point of the air touching it. Insulate cold pipes, ducts and windows, or lower the dew point with ventilation or dehumidification.

Below 0 °C the saturation pressure is taken over ice, so the answer is a frost point. Dew point and frost point differ by a degree or two near −10 °C.

Dew point depends a little on pressure only through the humidity ratio; the dew point itself does not change with altitude for a given vapor pressure. The relative humidity does, so use the station reading and not a sea-level-corrected one.

Comfort: a dew point under 10 °C (50 °F) feels dry, 10 to 16 °C (50 to 60 °F) is comfortable, 16 to 21 °C (60 to 70 °F) is humid and above 21 °C (70 °F) is oppressive.

Compressed air has a pressure dew point, the dew point at line pressure. It is much higher than the same air’s dew point at atmospheric pressure: pressure raises the vapor pressure by the same ratio as the total pressure.

Common questions

How do you calculate dew point from temperature and humidity?

Find the water vapor pressure (relative humidity times the saturation pressure at the air temperature), then find the temperature at which the saturation pressure equals that vapor pressure. For 25 °C and 50 % that is 13.9 °C. This calculator does both steps.

What is a good dew point for comfort?

Below 16 °C (60 °F) most people feel comfortable; above 21 °C (70 °F) the air feels oppressive. Relative humidity alone is misleading because it changes with temperature.

Is dew point the same as relative humidity?

No. Relative humidity is the water in the air compared with the most it could hold at that temperature. Dew point is the temperature at which it would be full. A 30 °C day at 50 % and a 10 °C day at 100 % feel nothing alike, although the first has a much higher dew point.

Why do windows fog in winter?

The glass is colder than the dew point of the room air, so water vapor condenses on it. Lower the indoor humidity or warm the glass (double glazing) to stop it.

Sources

  • ASHRAE Handbook – Fundamentals, Chapter 1 (Psychrometrics).
  • Hyland, R. W. and Wexler, A., Formulations for the Thermodynamic Properties of the Saturated Phases of H2O, ASHRAE Transactions 89(2A), 1983.

Last reviewed: November 2, 2026

Published by Nick Peterson, mechanical engineer.