Hazen-Williams Equation

Hazen-Williams equation for the head loss of water in a pipe: h = 10.67 L Q^1.852 / (C^1.852 D^4.87). Enter the flow, length, diameter and roughness coefficient C.

How it works

The Hazen-Williams equation is an empirical formula for the friction loss of water in a pipe. It is quick to use in water supply, sprinkler and irrigation design because the roughness is a single coefficient C and no friction factor iteration is needed.

hf = 10.67 × L × Q1.852 ÷ (C1.852 × D4.8704)

(SI: Q in m³/s, D and L in m)

SymbolMeaningSI unit
h_fHead lossm
LPipe lengthm
QFlow ratem³/s
CHazen-Williams roughness coefficient–
DInside diameterm

Typical C values: new plastic (PVC, PE) 150, new copper 140 to 150, new cast or ductile iron 130, old cast iron 100, galvanized steel 120, concrete 120. Higher C is smoother. The equation is valid for water at about 5 to 25 °C with velocities up to about 3 m/s and turbulent flow; it should not be used for other fluids or for hot water. Pressure drop follows from Δp = ρ g hf.

Related: Fluid Mechanics and Pipe Flow guide, Darcy-Weisbach equation. All formulas are listed in the Formulas library.

Worked example

10 L/s of water through 100 m of 100 mm pipe with C = 130: the velocity is 1.27 m/s and the head loss is 1.90 m, a pressure drop of 18.6 kPa.

Because the exponent on D is 4.87, going from 100 mm to 125 mm pipe cuts the loss by a factor of about 3.0.

Things to know

The formula is for water only. For oil, air or hot water use the Darcy-Weisbach equation.

C declines with age as pipes corrode and scale: design with the value for old pipe if the system must last decades.

US versions use the same formula with different constants (4.52 L Q^1.85 ÷ (C^1.85 d^4.87) for psi per foot, Q in gpm and d in inches); the calculator converts units so you can use either.

Common questions

What is the Hazen-Williams formula?

In SI units h = 10.67 L Q^1.852 ÷ (C^1.852 D^4.8704), with the head loss h and the length L and diameter D in meters and the flow Q in m³/s.

What is the C factor in Hazen-Williams?

The roughness coefficient: about 150 for smooth plastic, 130 for new iron, 100 for old pipe. A larger C means less friction.

When should you not use Hazen-Williams?

For fluids other than water near room temperature, for laminar flow, for very small pipes (under 50 mm) or for very high velocities. Use Darcy-Weisbach instead.

How do you convert head loss to pressure?

Multiply by the fluid density and gravity: Δp = ρ g h. For water, 1 m of head is 9.79 kPa, and 1 ft of head is 0.433 psi.

Sources

  • Williams, G. S. and Hazen, A., Hydraulic Tables, Wiley, 1933.
  • AWWA M22 and NFPA 13 for typical C values in water and sprinkler design.

Last reviewed: November 10, 2026

Published by Nick Peterson, mechanical engineer.