Power Factor Formula

Power factor = real power (kW) / apparent power (kVA). Enter the kW and kVA to get the power factor, the phase angle, the reactive power and the capacitor kvar needed to reach a target.

How it works

The power factor is the fraction of the apparent power (kVA) that does real work (kW). A motor or transformer draws reactive current that does no work; a low power factor means more current for the same useful power, bigger cables and often a utility surcharge.

PF = P ÷ S = cos φ

Q = √(S² − P²) = P tan φ

Qc = P (tan φ1 − tan φ2)

SymbolMeaningSI unit
PReal (active) powerkW
SApparent powerkVA
QReactive powerkvar
φPhase angle between voltage and currentdegrees
Q_cCapacitor kvar to correct from φ₁ to φ₂kvar

For a single-phase load S = V × I; for three-phase S = √3 × Vline × Iline. Induction motors run at a power factor of 0.7 to 0.9 depending on load. Correcting the power factor to 0.95 with capacitors reduces the current by the ratio of the old to the new factor, so a load drawn at 0.8 falls to 84 percent of its current at 0.95. Avoid over-correcting (a leading power factor) and avoid capacitors on circuits with large harmonic content without detuning reactors.

Related: Electrical Power guide (power factor and harmonics), Three-Phase Power Calculator. All formulas are listed in the Formulas library.

Worked example

A plant draws 80 kW at 100 kVA: PF = 80 ÷ 100 = 0.80 (φ = 36.9°) and the reactive power is √(100² − 80²) = 60 kvar. To reach a power factor of 0.95 it needs capacitors of Qc = 80 × (tan 36.87° − tan 18.19°) = 33.7 kvar.

The apparent power then falls to 80 ÷ 0.95 = 84.2 kVA, a 16 percent cut in the current.

Things to know

Displacement power factor (cos φ of the fundamental) ignores harmonics. True power factor also includes the distortion from non-linear loads such as drives and switch-mode supplies.

Capacitor banks should be switched or sized for the lightest load; over-correction at low load can raise the voltage.

A lagging power factor (current behind voltage) is inductive, typical of motors; a leading power factor is capacitive.

Common questions

What is the power factor formula?

PF = P ÷ S = cos φ, the real power in kW divided by the apparent power in kVA.

What is a good power factor?

0.95 or higher. Many utilities penalize below 0.9.

How do you correct a low power factor?

Add capacitors at the load or the service entrance sized by Qc = P (tan φ₁ − tan φ₂), or use a drive or motor with a better power factor.

What is the difference between kW, kVA and kvar?

kW is real power, kvar is reactive power that does no work, and kVA is their vector sum: S² = P² + Q².

Sources

  • IEEE Std 1459, Definitions for the Measurement of Electric Power Quantities.
  • Wildi, T., Electrical Machines, Drives and Power Systems, Pearson.

Last reviewed: November 10, 2026

Published by Nick Peterson, mechanical engineer.