Copper Tube Sizes Chart (Type K, L and M)

Copper water tube from 1/4 to 4 inch: outside diameter, wall thickness of Types K, L and M, bore and water content.

US copper water tube (ASTM B88) is named by a nominal size, but its real outside diameter is always 1/8 inch larger: “½ inch” tube measures 0.625 in across and “¾ inch” tube measures 0.875 in.

Three wall thicknesses share each outside diameter. Type K is the thickest (underground and severe service), Type L is the general-purpose grade, and Type M is the thinnest, used for domestic water and heating where codes allow. The table gives the outside diameter, the three walls, and the bore and water content of Type L.

The table

11 rows
Nominal size (in)Outside diameter (in)Outside diameter (mm)Wall, Type K (in)Wall, Type L (in)Wall, Type M (in)Inside diameter, Type L (in)Inside diameter, Type L (mm)Water held, Type L (US gal/ft)
1/40.3759.530.0350.03–0.31580.004
3/80.512.70.0490.0350.0250.4310.920.0075
1/20.62515.880.0490.040.0280.54513.840.0121
3/40.87522.230.0650.0450.0320.78519.940.0251
11.12528.580.0650.050.0351.02526.040.0429
1-1/41.37534.930.0650.0550.0421.26532.130.0653
1-1/21.62541.280.0720.060.0491.50538.230.0924
22.12553.980.0830.070.0581.98550.420.1608
2-1/22.62566.680.0950.080.0652.46562.610.2479
33.12579.380.1090.090.0722.94574.80.3539
44.125104.780.1340.110.0953.90599.190.6222

Source and notes: ASTM B88, Standard Specification for Seamless Copper Water Tube (nominal or standard sizes): the outside diameter is always 1/8 inch more than the nominal size. Inside diameter and contents are computed from the outside diameter and the Type L wall. Verify critical dimensions against the current standard or the tube maker.

How to use this table

  1. Identify a tube by measuring its outside diameter and subtracting 1/8 inch to get the nominal size.
  2. Read the wall thickness for the type you have (printed along the tube: green for K, blue for L, red for M).
  3. Use the bore for flow and pressure-drop calculations and the water content for system volume and hot-water wait times.

Worked example: ¾ inch Type L tube

  • Outside diameter = ¾ + ⅛ = 0.875 in (22.23 mm). The Type L wall is 0.045 in, so the bore is 0.875 − 2 × 0.045 = 0.785 in (19.94 mm).
  • It holds 0.0251 US gallons per foot, so a 40 ft run contains 1.00 gallons.
  • At 4 gallons per minute the velocity is 2.7 ft/s, well under the usual limit of 5 to 8 ft/s for cold water.

Notes and cautions

  • Refrigeration and air-conditioning tube (ACR, ASTM B280) is different: it is named by its actual outside diameter, so “⅝ inch ACR” is the same tube as “½ inch” water tube.
  • Copper tube sizes do not match steel pipe sizes. A ½ inch copper tube (0.625 in outside) is much smaller than ½ inch steel pipe (0.840 in outside).
  • Hard-drawn tube comes in straight lengths; annealed (soft) tube comes in coils and can be bent and flared.
  • Metric copper tube (EN 1057) is sized by outside diameter in millimeters, such as 15, 22 and 28 mm, and does not interchange with inch sizes without adapters.

FAQ

What is the outside diameter of ½ inch copper pipe?

0.625 in (15.88 mm). Copper water tube is always 1/8 inch larger than its nominal size.

What is the difference between Type K, L and M copper?

Wall thickness. For ¾ inch tube the walls are 0.065, 0.045 and 0.032 in. All three have the same outside diameter and use the same fittings.

Which type of copper pipe is used in houses?

Type L or Type M for water supply, depending on the local code. Type M costs less; Type L has more margin against corrosion and is required in some areas.

How is copper tube joined?

By soldering or brazing into capillary fittings, by press fittings, by compression fittings, or by flaring soft tube.

Sources

  • ASTM B88, Standard Specification for Seamless Copper Water Tube.
  • Copper Development Association, Copper Tube Handbook.
  • ASTM B88, Standard Specification for Seamless Copper Water Tube (nominal or standard sizes): the outside diameter is always 1/8 inch more than the nominal size. Inside diameter and contents are computed from the outside diameter and the Type L wall. Verify critical dimensions against the current standard or the tube maker.

Published by Nick Peterson, mechanical engineer.