Dew Point Chart (Temperature and Relative Humidity)
Dew point for air temperatures from 0 to 40 °C (32 to 104 °F) and relative humidity from 20 to 100 percent.
The dew point is the temperature to which air must be cooled, at constant pressure and moisture content, before water vapor begins to condense. Any surface colder than the dew point of the surrounding air will collect water: a cold glass, a chilled pipe, a window in winter, the inside of a poorly insulated wall. The dew point is also a direct measure of how much moisture the air holds, which makes it a better comfort indicator than relative humidity.
The chart gives the dew point for every 2 °C of air temperature and for relative humidity from 20 to 100 percent. At 100 percent the dew point is the same as the air temperature. The values are computed with the Magnus formula.
The table
| Air temperature (°C) | Air temperature (°F) | Dew point at 20 % RH (°C) | Dew point at 30 % RH (°C) | Dew point at 40 % RH (°C) | Dew point at 50 % RH (°C) | Dew point at 60 % RH (°C) | Dew point at 70 % RH (°C) | Dew point at 80 % RH (°C) | Dew point at 90 % RH (°C) | Dew point at 100 % RH (°C) |
|---|---|---|---|---|---|---|---|---|---|---|
| 0 | 32 | -20.3 | -15.5 | -12 | -9.2 | -6.8 | -4.8 | -3 | -1.4 | 0 |
| 2 | 35.6 | -18.7 | -13.8 | -10.2 | -7.4 | -5 | -2.9 | -1.1 | 0.5 | 2 |
| 4 | 39.2 | -17 | -12 | -8.4 | -5.5 | -3.1 | -1 | 0.9 | 2.5 | 4 |
| 6 | 42.8 | -15.3 | -10.3 | -6.6 | -3.7 | -1.2 | 0.9 | 2.8 | 4.5 | 6 |
| 8 | 46.4 | -13.6 | -8.6 | -4.8 | -1.8 | 0.7 | 2.9 | 4.8 | 6.5 | 8 |
| 10 | 50 | -12 | -6.8 | -3 | 0 | 2.6 | 4.8 | 6.7 | 8.4 | 10 |
| 12 | 53.6 | -10.3 | -5.1 | -1.2 | 1.9 | 4.5 | 6.7 | 8.7 | 10.4 | 12 |
| 14 | 57.2 | -8.7 | -3.3 | 0.6 | 3.7 | 6.4 | 8.6 | 10.6 | 12.4 | 14 |
| 16 | 60.8 | -7 | -1.6 | 2.4 | 5.6 | 8.2 | 10.5 | 12.5 | 14.4 | 16 |
| 18 | 64.4 | -5.3 | 0.1 | 4.2 | 7.4 | 10.1 | 12.4 | 14.5 | 16.3 | 18 |
| 20 | 68 | -3.7 | 1.9 | 6 | 9.3 | 12 | 14.4 | 16.4 | 18.3 | 20 |
| 22 | 71.6 | -2 | 3.6 | 7.8 | 11.1 | 13.9 | 16.3 | 18.4 | 20.3 | 22 |
| 24 | 75.2 | -0.4 | 5.3 | 9.6 | 12.9 | 15.8 | 18.2 | 20.3 | 22.3 | 24 |
| 26 | 78.8 | 1.3 | 7.1 | 11.4 | 14.8 | 17.6 | 20.1 | 22.3 | 24.2 | 26 |
| 28 | 82.4 | 2.9 | 8.8 | 13.1 | 16.6 | 19.5 | 22 | 24.2 | 26.2 | 28 |
| 30 | 86 | 4.6 | 10.5 | 14.9 | 18.4 | 21.4 | 23.9 | 26.2 | 28.2 | 30 |
| 32 | 89.6 | 6.2 | 12.3 | 16.7 | 20.3 | 23.3 | 25.8 | 28.1 | 30.2 | 32 |
| 34 | 93.2 | 7.9 | 14 | 18.5 | 22.1 | 25.1 | 27.8 | 30.1 | 32.1 | 34 |
| 36 | 96.8 | 9.5 | 15.7 | 20.3 | 23.9 | 27 | 29.7 | 32 | 34.1 | 36 |
| 38 | 100.4 | 11.1 | 17.4 | 22.1 | 25.8 | 28.9 | 31.6 | 33.9 | 36.1 | 38 |
| 40 | 104 | 12.8 | 19.1 | 23.8 | 27.6 | 30.8 | 33.5 | 35.9 | 38 | 40 |
Source and notes: Computed with the Magnus formula: γ = ln(RH ÷ 100) + 17.62 T ÷ (243.12 + T), dew point = 243.12 γ ÷ (17.62 − γ), with T in °C (Sonntag constants, accurate to about 0.35 °C between −45 and 60 °C). The psychrometric calculator on this site uses the more exact Hyland-Wexler equations; results agree to a few tenths of a degree.
How to use this table
- Find the row for the air temperature, then the column for the relative humidity.
- Compare the result with the temperature of the surface you are worried about. If the surface is colder than the dew point, expect condensation on it.
- For a comfort check, a dew point below about 16 °C feels comfortable, 16 to 18 °C is slightly humid, and above 21 °C feels oppressive.
Worked example: condensation on a cold pipe
- A workshop is at 24 °C (75.2 °F) and 60 percent relative humidity. Read the row for 24 °C and the 60 percent column: the dew point is 15.8 °C.
- A chilled-water pipe at 12 °C is below that dew point, so it will sweat. A pipe at 18 °C stays dry. Insulating the 12 °C pipe with a vapor barrier keeps its outer surface above the dew point.
- On a humid day at 30 °C and 70 percent the dew point is 23.9 °C, so even a drink at room temperature collects water.
Notes and cautions
- The Magnus formula is accurate to about 0.35 °C between −45 and 60 °C. The Psychrometric Calculator on this site uses the more exact Hyland–Wexler equations and agrees to a few tenths of a degree.
- Dew point depends on the moisture in the air, not on the air temperature: heating the air does not change its dew point, but raises the temperature of the room away from it, so relative humidity falls.
- Frost forms instead of dew when the surface is below 0 °C; the frost point is a little higher than the dew point at the same moisture content.
- Compressed-air systems quote a pressure dew point, which is the dew point of the air at line pressure and is much higher than the dew point after it expands to atmospheric pressure.
Related tools and guides
FAQ
What is the dew point?
The temperature at which air becomes saturated and water vapor starts to condense into liquid, for the amount of moisture the air actually holds.
What dew point is comfortable?
Most people find a dew point below about 16 °C (60 °F) comfortable, 16 to 21 °C slightly to quite humid, and above 21 °C (70 °F) oppressive.
How do I find the dew point from temperature and humidity?
Read this chart, or use the Magnus formula: γ = ln(RH ÷ 100) + 17.62 T ÷ (243.12 + T), then dew point = 243.12 γ ÷ (17.62 − γ), with T in °C.
Why does the dew point equal the air temperature at 100 percent humidity?
At 100 percent relative humidity the air is already saturated, so any cooling causes condensation straight away.
Sources
- Sonntag, D., Zeitschrift für Meteorologie 40 (1990): the constants used in the Magnus formula.
- ASHRAE Handbook, Fundamentals: Psychrometrics.
- Computed with the Magnus formula: γ = ln(RH ÷ 100) + 17.62 T ÷ (243.12 + T), dew point = 243.12 γ ÷ (17.62 − γ), with T in °C (Sonntag constants, accurate to about 0.35 °C between −45 and 60 °C). The psychrometric calculator on this site uses the more exact Hyland-Wexler equations; results agree to a few tenths of a degree.