AWG to mm2 Conversion Chart (Wire Size to Metric)
AWG wire sizes 0000 to 30 with diameter, area in mm², circular mils, the nearest standard metric size and copper resistance.
American wire gauge (AWG) numbers wire by steps in diameter: each gauge number is about 11 percent smaller in diameter than the one before it, and three gauges halve the area. The rest of the world sizes wire by the cross-sectional area in square millimeters, using the preferred series 0.5, 0.75, 1, 1.5, 2.5, 4, 6, 10, 16 and so on (IEC 60228). The table puts the two side by side.
For every AWG size from 0000 to 30 it gives the diameter in millimeters, the area in mm², the area in circular mils (the American unit: the diameter in thousandths of an inch, squared), the nearest standard metric cross-section and the resistance of copper wire at 20 °C.
The table
| AWG size | Diameter (mm) | Area (mm²) | Circular mils | Nearest standard metric size (mm²) | Copper resistance at 20 °C (Ω/km) |
|---|---|---|---|---|---|
| AWG 0000 | 11.684 | 107.219 | 2116 | 120 | 0.161 |
| AWG 000 | 10.405 | 85.029 | 167806 | 95 | 0.203 |
| AWG 00 | 9.266 | 67.431 | 133077 | 70 | 0.256 |
| AWG 0 | 8.251 | 53.475 | 105535 | 50 | 0.322 |
| AWG 1 | 7.348 | 42.408 | 83693 | 50 | 0.407 |
| AWG 2 | 6.544 | 33.631 | 66371 | 35 | 0.513 |
| AWG 3 | 5.827 | 26.67 | 52635 | 25 | 0.646 |
| AWG 4 | 5.189 | 21.151 | 41741 | 25 | 0.815 |
| AWG 5 | 4.621 | 16.773 | 33102 | 16 | 1.028 |
| AWG 6 | 4.115 | 13.302 | 26251 | 16 | 1.296 |
| AWG 7 | 3.665 | 10.549 | 20818 | 10 | 1.634 |
| AWG 8 | 3.264 | 8.366 | 16510 | 10 | 2.061 |
| AWG 9 | 2.906 | 6.634 | 13093 | 6 | 2.599 |
| AWG 10 | 2.588 | 5.261 | 10383 | 6 | 3.277 |
| AWG 11 | 2.305 | 4.172 | 8234 | 4 | 4.132 |
| AWG 12 | 2.053 | 3.309 | 6530 | 4 | 5.21 |
| AWG 13 | 1.828 | 2.624 | 5178 | 2.5 | 6.57 |
| AWG 14 | 1.628 | 2.081 | 4107 | 2.5 | 8.285 |
| AWG 15 | 1.45 | 1.65 | 3257 | 1.5 | 10.447 |
| AWG 16 | 1.291 | 1.309 | 2583 | 1.5 | 13.173 |
| AWG 17 | 1.15 | 1.038 | 2048 | 1 | 16.611 |
| AWG 18 | 1.024 | 0.823 | 1624 | 0.75 | 20.947 |
| AWG 19 | 0.912 | 0.653 | 1288 | 0.75 | 26.413 |
| AWG 20 | 0.812 | 0.518 | 1022 | 0.5 | 33.306 |
| AWG 21 | 0.723 | 0.41 | 810 | 0.5 | 41.999 |
| AWG 22 | 0.644 | 0.326 | 642 | 0.5 | 52.959 |
| AWG 23 | 0.573 | 0.258 | 509 | 0.5 | 66.78 |
| AWG 24 | 0.511 | 0.205 | 404 | 0.5 | 84.208 |
| AWG 25 | 0.455 | 0.162 | 320 | 0.5 | 106.185 |
| AWG 26 | 0.405 | 0.129 | 254 | 0.5 | 133.897 |
| AWG 27 | 0.361 | 0.102 | 202 | 0.5 | 168.84 |
| AWG 28 | 0.321 | 0.081 | 160 | 0.5 | 212.904 |
| AWG 29 | 0.286 | 0.064 | 127 | 0.5 | 268.467 |
| AWG 30 | 0.255 | 0.051 | 101 | 0.5 | 338.53 |
Source and notes: AWG diameters follow d = 0.127 mm × 92^((36 − n) ÷ 39) (n = 36 for AWG 36; 0000 is n = −3). Circular mils are the diameter in mils squared. The nearest metric size is the standard IEC 60228 cross-section (0.5 to 300 mm²) closest in area; the nearest size is a guide only, and ampacity and voltage-drop rules differ between AWG (NEC) and metric (IEC) practice. Resistance uses copper at 1.724 × 10⁻⁸ Ω m.
How to use this table
- Find the AWG size and read the area. Compare it with the metric size in the next column to see what an imported cable or a drawing calls for.
- The nearest metric size is a guide, not a substitute: always check the current rating in the code that applies (NEC for AWG, IEC 60364 or local codes for metric).
- Use the resistance column to estimate voltage drop: drop = current × resistance per kilometer × length ÷ 1,000.
Worked example: matching an AWG cable to a metric size
- AWG 10 has a diameter of 2.588 mm and an area of 5.26 mm² (10,383 circular mils). The nearest standard metric size is 6 mm², slightly larger.
- AWG 14 is 2.08 mm², between the 1.5 and 2.5 mm² metric sizes (nearest: 2.5 mm²). Replacing 14 AWG wire with 1.5 mm² wire gives a thinner conductor; replacing it with 2.5 mm² is a safe upgrade.
- At 20 °C, 100 m of AWG 14 copper has a resistance of 0.83 Ω, so 10 A through 100 m of wire (200 m of conductor for the loop) drops about 16.6 V.
Notes and cautions
- Three AWG steps halve or double the area, and six steps halve or double the diameter. AWG 10 is about twice the area of AWG 13, and AWG 40 is a hair-thin wire.
- The same AWG number can describe a solid wire or a stranded one; stranded wire has the same area of copper but a slightly larger overall diameter.
- Ampacity depends on insulation, temperature, bundling and ambient, so do not size wire from the area alone. See the Wire Ampacity and Voltage Drop Calculator.
- Large cables above AWG 0000 are sized in kcmil (thousands of circular mils): 250 kcmil is about 127 mm².
Related tools and guides
- AWG Wire Gauge Table
- Wire Ampacity and Voltage Drop Calculator
- Resistivity of metals and alloys
- All reference tables
FAQ
How do I convert AWG to mm²?
Use the table, or compute the diameter d = 0.127 × 92^((36 − n) ÷ 39) mm and the area π d² ÷ 4. For example, AWG 14 is 2.08 mm² and AWG 10 is 5.26 mm².
What AWG is 2.5 mm²?
About AWG 13 (2.62 mm²). AWG 14 (2.08 mm²) is a little smaller, so 2.5 mm² cable is not an exact match for either.
What is a circular mil?
The area of a circle one mil (0.001 inch) in diameter, about 0.000,506 7 mm². The area of a round wire in circular mils is its diameter in mils squared.
Are AWG and SWG the same?
No. British Standard Wire Gauge (SWG) is a different series with different diameters. AWG is the American system and is used for electrical wire.
Sources
- ASTM B258, Standard Specification for Nominal Diameters and Cross-Sectional Areas of AWG Sizes of Solid Round Wires.
- IEC 60228, Conductors of insulated cables.
- AWG diameters follow d = 0.127 mm × 92^((36 − n) ÷ 39) (n = 36 for AWG 36; 0000 is n = −3). Circular mils are the diameter in mils squared. The nearest metric size is the standard IEC 60228 cross-section (0.5 to 300 mm²) closest in area; the nearest size is a guide only, and ampacity and voltage-drop rules differ between AWG (NEC) and metric (IEC) practice. Resistance uses copper at 1.724 × 10⁻⁸ Ω m.